Office ventilation comes down to one number: how much fresh outdoor air each room needs. Once you have that figure, choosing the fan is straightforward. This guide shows you how to calculate it using the current Building Regulations, works through a 10-person office and a meeting room, and recommends the inline, box and heat recovery units we supply for each job.

Quick answer: Approved Document F (Volume 2, 2021 edition) asks for at least 10 l/s of outdoor air per person in offices, or 1 l/s per m² of floor area if that is higher. A 10-person office therefore needs about 100 l/s (360 m³/h) of supply and a matching extract. For most small offices, a pair of Vent-Axia ACM150 inline mixed-flow fans (£238.99 each, up to 576 m³/h free air) or ACM200 (£380.03, up to 1044 m³/h) for longer duct runs handles supply and extract. Where noise matters, use the insulated Systemair KVK Slim 200 EC box fan (£724.11). For small offices that want to recover heat, consider the Vent-Axia Sentinel Econiq S MVHR (£1,719.83).

How much fresh air does an office need?

In England, ventilation for offices is covered by Approved Document F, Volume 2: Buildings other than dwellings (2021 edition). The key figures for offices are:

Space Approved Document F Volume 2 requirement
Occupiable office rooms Outdoor air at whichever is higher: 10 l/s per person, or 1 l/s per m² floor area
Corridors and lift lobbies (common spaces) Mechanical supply of 0.5 l/s per m², or natural openings of at least 1/50 of floor area
Toilets and washrooms Intermittent extract of 6 l/s per WC pan or urinal, and 15 l/s per shower or bath
Kitchenette (microwave and drinks only) 15 l/s extract
Kitchenette with domestic hob 30 l/s if the extract is adjacent to the hob, 60 l/s if remote from it
Printer and photocopier rooms (heavy use) 20 l/s per machine during use

Approved Document F also expects new offices to have a way of monitoring indoor air quality, such as CO₂ monitors, in most occupiable rooms. Its guidance treats sustained CO₂ above 1,500 ppm as a sign of inadequate ventilation. CIBSE guidance uses similar per-person rates and is the usual reference for detailed design. For an overview of the regulations, see our guide to Building Regulations Part F.

Useful conversion: 1 l/s = 3.6 m³/h. Fan catalogues usually quote m³/h, so multiply your l/s figure by 3.6.

Worked example: 10-person office and meeting room

Open office: 10 people in a 70 m² room.

  • Per person: 10 people x 10 l/s = 100 l/s
  • Per floor area: 70 m² x 1 l/s = 70 l/s
  • Use the higher figure: 100 l/s = 360 m³/h of supply, with a matching extract

Meeting room: seats 8 people, 25 m².

  • Per person: 8 x 10 l/s = 80 l/s
  • Per floor area: 25 x 1 l/s = 25 l/s
  • Use the higher figure: 80 l/s = 288 m³/h

Size meeting rooms for their maximum seated capacity, not average use. They fill up, the door shuts and CO₂ climbs fast.

Choosing the fan: catalogue airflow is usually quoted at free air (no ductwork). Real systems with ducting, grilles, a filter and a louvre add resistance, so the fan delivers less. Give yourself headroom and check the fan curve at your system pressure.

Room Design airflow Short duct run Longer run or filter and heater
10-person office 360 m³/h ACM150 (up to 576 m³/h free air) ACM200 (up to 1044 m³/h) or KVK Slim 200 EC (up to 936 m³/h)
8-person meeting room 288 m³/h ACM150 (up to 576 m³/h) KVK Slim 160 EC (up to 533 m³/h) or ACM200

You need one fan for supply and one for extract in each system, unless a single extract fan with make-up air through transfer grilles and an inlet louvre is acceptable for the space. Fans with speed control let you commission to the exact rate rather than running flat out.

Common mistake: fitting extract only. Without a planned supply path, the fan pulls air under doors and through gaps, the office goes negative and the fan never reaches its rated airflow. Plan supply and extract together, and add a filter box and, if needed, a duct heater on the supply side so winter air is not cold.

Which fan type: inline, box fan or MVHR?

Fan type Best for Pros Watch out for
Inline mixed-flow Small offices, single rooms, toilet extract Compact, low cost, around 2.5x the pressure of an axial fan, fits in a ceiling void Uninsulated casing; add silencers in quiet rooms
Insulated box fan Meeting rooms, offices where noise matters Acoustically lined casing, EC motors with 0-10 V speed control Larger and more expensive than inline fans
MVHR Offices where heat loss and comfort matter Supply and extract in one unit, recovers heat from outgoing air Higher cost, needs space and both duct networks; larger offices need commercial air handling units

For more on how mixed-flow fans work, read What is a mixed flow extractor fan?. If you are comparing inline models, see our inline duct fans ranked by our experts.

Noise targets for offices

Ventilation noise is the most common complaint after an office fit-out. CIBSE Guide A gives recommended noise ratings (NR) for building services noise. Typical ranges are:

Space Typical NR target Approx. dB(A)
Meeting rooms and boardrooms NR 25 to 35 30 to 40 dB(A)
Private or cellular offices NR 30 to 35 35 to 40 dB(A)
Open-plan offices NR 35 to 40 40 to 45 dB(A)
Corridors, toilets NR 40 to 45 45 to 50 dB(A)

These are maximums; aim lower where you can. Practical ways to hit them:

  • Size the fan so it runs at part speed at your design airflow, not flat out.
  • Fit a circular silencer either side of the fan, such as the Systemair LDC 200 mm x 600 mm silencer (£113.99) or 125 mm x 600 mm (£81.99).
  • Keep the fan out of the occupied room: in a ceiling void over a corridor or store.
  • Keep duct velocities down by not undersizing ducts and grilles.
  • Use flexible connectors and anti-vibration mounts to stop vibration travelling through the structure.

More detail in how contractors reduce noise in commercial ventilation systems.

Our office fan picks

Vent-Axia ACM150 inline mixed flow fan

Best for a small office or meeting room: Vent-Axia ACM150 £238.99
Inline mixed-flow fan for 150 mm duct, up to 576 m³/h free air. Three-speed AC motor, speed controllable through a Vent-Axia controller, IP44, Class II, runs horizontally or vertically. The removable motor core and detachable spigots make maintenance easy. Covers our 10-person office and meeting room examples on short runs. View the ACM150.

Vent-Axia ACM200 inline mixed flow fan

Best for longer duct runs: Vent-Axia ACM200 £380.03
Up to 1044 m³/h free air through 200 mm duct, with the same three-speed motor and IP44 polymer casing. The extra capacity covers filter boxes, heaters and longer runs, and serves 15 to 25 people depending on system resistance. For larger open-plan areas, the galvanised ACM250 (£594.99, up to 1620 m³/h, IP54) steps up again. View the ACM200.

Systemair KVK Slim 200 EC insulated box fan

Best quiet box fan: Systemair KVK Slim 200 EC £724.11
Insulated box fan with 200 mm circular connections, up to 936 m³/h. EC motor with a pre-wired 0-10 V potentiometer for 0 to 100% speed control, low SFP, AluZinc C4 casing and a slim profile for tight ceiling voids. The 160 mm KVK Slim 160 EC (£540.99, up to 533 m³/h) suits a single meeting room. For the quietest option, the fully insulated KVK Silent 200 EC (£1,034.99) is lined with high-density mineral wool. View the KVK Slim 200 EC.

Vent-Axia Sentinel Econiq S MVHR unit

Best heat recovery for a small office: Vent-Axia Sentinel Econiq S 499883 £1,719.83
Up to 93% heat recovery and up to 97 l/s at 150 Pa, with sound levels as low as 15.5 dB(A), a humidity sensor, automatic summer bypass and frost protection. It is designed as a whole-house unit, so at 10 l/s per person it suits a small office or studio of up to around nine people. Larger offices need a commercial air handling unit; ask us. Browse more in MVHR units. View the Sentinel Econiq S.

Toilet and kitchenette extract

Office toilets and tea points are extract-only spaces, kept at negative pressure so smells do not spread.

Toilet example: a washroom with 3 WCs and 1 urinal needs 4 x 6 l/s = 24 l/s (about 86 m³/h). Add 15 l/s for each shower.

Kitchenette example: a tea point with a kettle and microwave needs 15 l/s (54 m³/h). If there is a domestic hob, that rises to 30 l/s next to the hob or 60 l/s if the extract is remote from it.

Vent-Axia ACM125T inline mixed flow fan with timer

Best for a single washroom or tea point: Vent-Axia ACM125T £196.99
125 mm inline mixed-flow fan, up to 324 m³/h free air, with a built-in adjustable run-on timer so it keeps clearing the room after the lights go off. Vent-Axia lists office, toilet and commercial extract among its uses. The non-timer ACM100 (£146.99, up to 288 m³/h) suits smaller washrooms on a switched or continuous circuit. View the ACM125T.

Vent-Axia Multivent Lo-Carbon MVDC-MS central extract unit

Best for several toilets from one unit: Vent-Axia Multivent Lo-Carbon MVDC-MS £253.99
A central extract unit with three 125 mm spigots, so one fan can serve a run of WCs and a tea point. DC motor with fully variable normal, purge and boost speeds, acoustic lining as standard, and wall, ceiling or loft mounting. Vent-Axia lists multi-point commercial extract among its uses. View the Multivent MVDC-MS.

Send us your floor plan and we'll size it. Tell us the room sizes, occupancy, duct route lengths and any noise targets. We will recommend supply and extract fans, silencers and grilles, and confirm stock and lead times. Call 0161 399 3825 or get in touch.

FAQs

How much ventilation does an office need per person?

Approved Document F Volume 2 (2021) asks for at least 10 l/s of outdoor air per person in occupiable office rooms, or 1 l/s per m² of floor area if that gives a higher total. For 10 people that is 100 l/s, or 360 m³/h.

What size inline duct fan do I need for an office?

Work out the airflow first (people x 10 l/s x 3.6 = m³/h), then choose a fan with headroom above that at your system pressure. For a 10-person office on a short run, a Vent-Axia ACM150 (up to 576 m³/h free air) is a typical choice. Longer runs with filters and heaters suit the ACM200.

Do I need supply and extract, or just an office extractor fan?

For proper fresh air you need both a supply route and an extract route. Extract only works if replacement air can get in through a planned inlet such as a louvre or transfer grille. In most offices, balanced supply and extract fans, or MVHR, give the most reliable result.

How quiet should office ventilation be?

CIBSE Guide A typically recommends NR 35 to 40 for open-plan offices, NR 30 to 35 for private offices and NR 25 to 35 for meeting rooms. Insulated box fans, silencers and running fans at part speed help meet those targets.

What extract rate do office toilets need?

Approved Document F Volume 2 asks for intermittent extract of 6 l/s per WC pan or urinal, plus 15 l/s per shower. A washroom with four WCs needs 24 l/s, about 86 m³/h.