A volume control damper, also called a balancing damper, is an adjustable blade inside the duct that sets how much air flows down each branch, so every room or grille in a ventilation system gets its design airflow. We stock single blade circular volume control dampers in galvanised steel from 100mm to 355mm, with a manual handle that locks the blade in position without tools, for next working day delivery. Multileaf dampers for rectangular ductwork and motorised dampers for BMS control can be sourced to order. For sizing or a project schedule, email hello@efans.co.uk or call 0161 399 3825.
Read moreRead less
Frequently asked questions
What is a volume control damper?
A volume control damper is a manually set blade or set of blades fitted in a duct to restrict and regulate airflow. In a system with several branches, air naturally takes the easiest path, so branches near the fan get too much and the furthest rooms too little. Fitting a volume control damper in each branch lets the installer trim the airflow until every outlet delivers its design rate. Once set, the damper is locked so the system stays balanced.
Single blade or multileaf damper?
A single blade damper has one pivoting disc and is the standard choice for circular ductwork up to about 355mm. It is compact and simple to set. A multileaf damper has several smaller blades, usually opposed, which gives finer, more even control and suits rectangular ductwork and larger duct sizes. We stock single blade circular dampers from 100mm to 355mm and can source multileaf dampers to order.
Where should a volume control damper be fitted?
Fit one in each branch that needs balancing, as close to the branch take-off as is practical, so it controls that run on its own. Install it in a straight section of duct, away from bends, fans and grilles where possible, because turbulent air makes the setting less stable and can cause noise. Make sure the handle stays accessible after ceilings go in, because the system may need rebalancing later.
How do I balance a system with volume control dampers?
Start with all dampers fully open. Measure the airflow at each terminal, then partly close the dampers on the branches that are getting more than their share, working from the outlets nearest the fan outwards, until every outlet is within its design figure. Lock each handle and mark the set position. This is normally done during commissioning with an anemometer or flow hood.
What are the temperature and pressure limits?
Our single blade circular dampers are rated for air up to 80°C and duct pressure up to 500 Pa, which covers general supply and extract ventilation. They are a low-tightness damper, designed to regulate airflow rather than seal a duct shut. For hot or grease-laden air, high pressure systems or a tight shut-off, ask us for a suitable alternative.
Volume control damper, fire damper or non return damper?
They do different jobs. A volume control damper sets the airflow and stays where you put it. A non return damper opens with the airflow and closes when the fan stops, to stop air flowing backwards. A fire damper closes automatically in a fire where a duct passes through a fire-rated wall or floor. Where you need both fire protection and airflow control at one point, the BSB FD-C is a combination fire and volume control damper.
Can I get a motorised volume control damper?
The dampers we stock are manual. Where airflow needs to change automatically, for example from a BMS, a CO2 sensor or a time schedule, you need a motorised damper with an actuator. We can source motorised dampers to order, so send us the duct size, the control signal and the supply voltage.
Do you supply volume control dampers for trade and projects?
Yes. We supply M&E contractors, ventilation installers and commissioning engineers. Send a damper schedule and we will price stock circular dampers and source multileaf or motorised dampers alongside. Call 0161 399 3825 or email hello@efans.co.uk.