Elta SH125-1LC Hideaway Low Profile Acoustic Box Fan EC - 125mm
Suggested products
Free 14 day returns
Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.
Why choose eFans?
- Bulk pricing available
- Free help and advice
- Fast quotes, usually within the hour
- Huge range with next-day delivery
- Credit accounts available
Delivery and Warranty
Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days.
£7.95
Next Working Day Delivery
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays)
£15.95
Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95
Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95
Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95
Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95
Product Details
Downloads
Specifications
Product specifications
| Model | SH125-1LC |
| Type | Low profile acoustic box fan |
| Size | 125mm circular spigots |
| Max airflow | 277 m³/h |
| Static pressure | 200 Pa |
| Motor | Single phase EC, 220-240V 50/60Hz, 5000 rpm |
| Power | 27 W at best efficiency point (0.25 A peak) |
| Noise | 47 dB(A) inlet, 48 dB(A) outlet, 36 dB(A) breakout at 3m |
| IP rating | IPX4 motor |
| Warranty | 1 Year Manufacturer |
Summary
See more specification See less specification
The Elta SH125-1LC is a 125mm Hideaway SH low profile acoustic box fan, built for ducted extract or supply where the ceiling void is too shallow for a standard box fan. It moves up to 277 m³/h in free air and 216 m³/h at 100 Pa, and Elta's published table runs out at 200 Pa, where airflow has fallen to 72 m³/h.
A single phase EC motor (220-240V 50/60Hz) drives a jet design double mixed flow impeller at up to 5000 rpm, drawing 27 W at best efficiency (0.25 A peak). An integrated commissioning control sets a single speed or a maximum speed, and the fan also accepts a potentiometer, 0-10V or PWM signal. The 1.2mm galvanised steel casing has a Class O fire rated acoustic lining and a removable lid, the motor is IPX4 with sealed for life bearings, and Elta give a 12 month warranty.
- 1 Phase
- EC Motor
- Up to 277 m³/h
- Speed Controllable
What it is best used for
Bathroom, shower room and small kitchen extract on 125mm duct in apartments, hotel bedrooms and residential refurbishments where the void above the ceiling is shallow. At 100 Pa it moves 216 m³/h, roughly 10 air changes an hour in a space of about 20 m³.
Elta's figures stop at 200 Pa and airflow falls away quickly above 100 Pa, so it is not the fan for long runs with filters and heater batteries; the Singleflow SSDL box fan holds its airflow to 500 Pa. It is not suitable for corrosive or explosive atmospheres, and air must stay between -20°C and +60°C.
Why choose this over alternatives
The Hideaway is the low profile option. Compared with the Elta SSDL125-1EC Singleflow box fan for the same 125mm duct, it gives 216 against 547 m³/h at 100 Pa and 72 against 493 m³/h at 200 Pa, so choose the Hideaway when void depth is the constraint and the SSDL when you need more pressure.
If you need more air, the Elta SH150-1LC moves 450 m³/h at 100 Pa. On a smaller duct the Elta SH100-1LC gives 155 m³/h at 100 Pa. Its specific fan power is 0.44 W/(L/s) at 100 Pa, which helps with Part L compliance.
Installation notes
- Mount it at any angle, adequately supported, and leave access to the removable lid for cleaning and maintenance.
- The circular spigots take 125mm duct directly; secure each joint with an Elta 018-125-CLAMP fast clamp, and check the airflow direction arrow before fixing.
- The fan comes with a 1m flying lead. Wire to Elta diagram 152-554 and fit a local means of isolation as the wiring regulations require.
- Speed is set on the built-in commissioning potentiometer. To use an external potentiometer or a 0-10V signal, remove the jumper link and connect to ST1; the commissioning setting then caps the maximum speed.
- Site the discharge so exhaust cannot be drawn back into a room through the open flue of a gas or fuel burning appliance, and inspect the fan at least every 12 months.
You'll also need
- Elta EC electronic controller 149-POT-10-MI (the potentiometer controller Elta list for every Hideaway SH)
- Elta fast clamps 018-125-CLAMP and backdraught damper 018-125-DAMPER available to order, ask us
- Elta panel filter 018-0125-FILT-P and heater battery 018-CV12-12-1M for supply duties available to order, ask us
Browse more commercial box fans, inline duct fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SH125-1LC |
| Type | Low profile acoustic box fan |
| Size | 125mm circular spigots |
| Max airflow | 277 m³/h |
| Static pressure | 200 Pa |
| Motor | Single phase EC, 220-240V 50/60Hz, 5000 rpm |
| Power | 27 W at best efficiency point (0.25 A peak) |
| Noise | 47 dB(A) inlet, 48 dB(A) outlet, 36 dB(A) breakout at 3m |
| IP rating | IPX4 motor |
| Warranty | 1 Year Manufacturer |
| Airflow at 100 Pa | 216 m³/h |
| Airflow at 200 Pa | 72 m³/h |
| Airflow at 7.5V control signal | 230 m³/h free air, 162 m³/h at 100 Pa, 43 dB(A) inlet |
| Speed control | Built-in commissioning potentiometer, 0-10V, PWM or external potentiometer input |
| Overall efficiency | 30.1% at best efficiency point |
| SFP at 100 Pa | 0.44 W/(L/s) |
| Impeller | Jet design double mixed flow, direct drive |
| Casing | 1.2mm galvanised steel, Class O acoustic lining, removable lid |
| Operating temperature | -20°C to +60°C, up to 95% RH |
| Weight | 5 kg |
| Electrical connection | 1m flying lead |
| Wiring diagram | 152-554 |
| ErP | Regulation (EU) 1253/2014, NRVU |
Manuals & Guides
Product Description
The Elta SH125-1LC is a 125mm Hideaway SH low profile acoustic box fan, built for ducted extract or supply where the ceiling void is too shallow for a standard box fan. It moves up to 277 m³/h in free air and 216 m³/h at 100 Pa, and Elta's published table runs out at 200 Pa, where airflow has fallen to 72 m³/h.
A single phase EC motor (220-240V 50/60Hz) drives a jet design double mixed flow impeller at up to 5000 rpm, drawing 27 W at best efficiency (0.25 A peak). An integrated commissioning control sets a single speed or a maximum speed, and the fan also accepts a potentiometer, 0-10V or PWM signal. The 1.2mm galvanised steel casing has a Class O fire rated acoustic lining and a removable lid, the motor is IPX4 with sealed for life bearings, and Elta give a 12 month warranty.
- 1 Phase
- EC Motor
- Up to 277 m³/h
- Speed Controllable
What it is best used for
Bathroom, shower room and small kitchen extract on 125mm duct in apartments, hotel bedrooms and residential refurbishments where the void above the ceiling is shallow. At 100 Pa it moves 216 m³/h, roughly 10 air changes an hour in a space of about 20 m³.
Elta's figures stop at 200 Pa and airflow falls away quickly above 100 Pa, so it is not the fan for long runs with filters and heater batteries; the Singleflow SSDL box fan holds its airflow to 500 Pa. It is not suitable for corrosive or explosive atmospheres, and air must stay between -20°C and +60°C.
Why choose this over alternatives
The Hideaway is the low profile option. Compared with the Elta SSDL125-1EC Singleflow box fan for the same 125mm duct, it gives 216 against 547 m³/h at 100 Pa and 72 against 493 m³/h at 200 Pa, so choose the Hideaway when void depth is the constraint and the SSDL when you need more pressure.
If you need more air, the Elta SH150-1LC moves 450 m³/h at 100 Pa. On a smaller duct the Elta SH100-1LC gives 155 m³/h at 100 Pa. Its specific fan power is 0.44 W/(L/s) at 100 Pa, which helps with Part L compliance.
Installation notes
- Mount it at any angle, adequately supported, and leave access to the removable lid for cleaning and maintenance.
- The circular spigots take 125mm duct directly; secure each joint with an Elta 018-125-CLAMP fast clamp, and check the airflow direction arrow before fixing.
- The fan comes with a 1m flying lead. Wire to Elta diagram 152-554 and fit a local means of isolation as the wiring regulations require.
- Speed is set on the built-in commissioning potentiometer. To use an external potentiometer or a 0-10V signal, remove the jumper link and connect to ST1; the commissioning setting then caps the maximum speed.
- Site the discharge so exhaust cannot be drawn back into a room through the open flue of a gas or fuel burning appliance, and inspect the fan at least every 12 months.
You'll also need
- Elta EC electronic controller 149-POT-10-MI (the potentiometer controller Elta list for every Hideaway SH)
- Elta fast clamps 018-125-CLAMP and backdraught damper 018-125-DAMPER available to order, ask us
- Elta panel filter 018-0125-FILT-P and heater battery 018-CV12-12-1M for supply duties available to order, ask us
Browse more commercial box fans, inline duct fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SH125-1LC |
| Type | Low profile acoustic box fan |
| Size | 125mm circular spigots |
| Max airflow | 277 m³/h |
| Static pressure | 200 Pa |
| Motor | Single phase EC, 220-240V 50/60Hz, 5000 rpm |
| Power | 27 W at best efficiency point (0.25 A peak) |
| Noise | 47 dB(A) inlet, 48 dB(A) outlet, 36 dB(A) breakout at 3m |
| IP rating | IPX4 motor |
| Warranty | 1 Year Manufacturer |
| Airflow at 100 Pa | 216 m³/h |
| Airflow at 200 Pa | 72 m³/h |
| Airflow at 7.5V control signal | 230 m³/h free air, 162 m³/h at 100 Pa, 43 dB(A) inlet |
| Speed control | Built-in commissioning potentiometer, 0-10V, PWM or external potentiometer input |
| Overall efficiency | 30.1% at best efficiency point |
| SFP at 100 Pa | 0.44 W/(L/s) |
| Impeller | Jet design double mixed flow, direct drive |
| Casing | 1.2mm galvanised steel, Class O acoustic lining, removable lid |
| Operating temperature | -20°C to +60°C, up to 95% RH |
| Weight | 5 kg |
| Electrical connection | 1m flying lead |
| Wiring diagram | 152-554 |
| ErP | Regulation (EU) 1253/2014, NRVU |
Manuals & Guides
Delivery & Returns
Our Price Match Promise
Payment Methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
How much air does the Elta SH125-1LC move?
Up to 277 m³/h in free air at full speed, 216 m³/h at 100 Pa and 72 m³/h at 200 Pa.
How do I control the speed?
The built-in commissioning potentiometer sets a single speed or a maximum speed. For user control, Elta list the 149-POT-10-MI EC controller, which we stock, or you can feed a 0-10V or PWM signal after removing the jumper link.
How quiet is it?
At full speed Elta quote 47 dB(A) at the inlet, 48 dB(A) at the outlet and 36 dB(A) breakout at 3m. Turned down to 7.5V the inlet figure drops to 43 dB(A).
What makes it low profile?
The Hideaway casing is redesigned to be slimmer than a standard box fan so it fits very shallow ceiling voids, and Elta say the new casing also improves airflow and lowers specific fan power. Check the exact casing dimensions on Elta's dimensional drawing against your void.
Can it be mounted on its side or outside?
It can be mounted at any angle. The motor is IPX4 and Elta's current datasheet rates the Hideaway SH as suitable for external mounting, with air from -20°C to +60°C.
What power supply does it need?
A single phase 220 to 240V 50/60Hz supply. Peak current is 0.25 A and it is supplied with a 1m flying lead for wiring by a qualified electrician (Elta diagram 152-554).