Elta SSDL400-1EC-RT Singleflow Centrifugal Box Fan Single Phase EC - 400mm (rectangular spigots and terminal box)
Elta SSDL400-1EC-RT Singleflow Centrifugal Box Fan Single Phase EC - 400mm (rectangular spigots and terminal box)
£2,386.99
SKU: SSDL400-1EC-RT

Elta SSDL400-1EC-RT Singleflow Centrifugal Box Fan Single Phase EC - 400mm (rectangular spigots and terminal box)

1 Phase
EC Motor
Up to 4414 m³/h
Out of stock
Not sure what you need? Email the teamhello@efans.co.uk
Free 14 day returns

Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.

Why choose eFans?
  • Bulk pricing available
  • Free help and advice
  • Fast quotes, usually within the hour
  • Huge range with next-day delivery
  • Credit accounts available
Delivery and Warranty

Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days. 
£7.95  

Next Working Day Delivery 
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays) 
£15.95 

Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95

Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95 

Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95

Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95 

Product Details

Specifications

Product specifications
Model SSDL400-1EC-RT
Type Centrifugal box fan, rectangular spigots, terminal box
Size 400mm (rectangular spigots)
Max airflow 4414 m³/h
Static pressure 500 Pa
Motor Single phase EC, 220-240V 50/60Hz, 1620 rpm
Power 754 W at best efficiency point (5.19 A peak)
Noise 58 dB(A) inlet, 60 dB(A) outlet, 43 dB(A) breakout at 3m
IP rating IP44 motor
Warranty 1 Year Manufacturer

Summary

The Elta SSDL400-1EC-RT is a 400mm Singleflow SSDL centrifugal box fan with rectangular inlet and outlet spigots and a pre-fitted terminal box. It moves up to 4414 m³/h in free air, 3722 m³/h at 200 Pa and still 2390 m³/h at 500 Pa, the highest pressure in Elta's published table.

A single phase EC external rotor motor (220-240V 50/60Hz) drives a backward curved impeller balanced to ISO1940-1, at up to 1620 rpm with an integrated commissioning control for setting speed. The 1.2mm galvanised steel casing is acoustically lined and suitable for external mounting, the IP44 motor has sealed for life bearings and runs in air from -20°C to +60°C, and Elta backs it with a 12 month warranty.

See more specification See less specification

The Elta SSDL400-1EC-RT is a 400mm Singleflow SSDL centrifugal box fan with rectangular inlet and outlet spigots and a pre-fitted terminal box. It moves up to 4414 m³/h in free air, 3722 m³/h at 200 Pa and still 2390 m³/h at 500 Pa, the highest pressure in Elta's published table.

A single phase EC external rotor motor (220-240V 50/60Hz) drives a backward curved impeller balanced to ISO1940-1, at up to 1620 rpm with an integrated commissioning control for setting speed. The 1.2mm galvanised steel casing is acoustically lined and suitable for external mounting, the IP44 motor has sealed for life bearings and runs in air from -20°C to +60°C, and Elta backs it with a 12 month warranty.

  • 1 Phase
  • EC Motor
  • Up to 4414 m³/h
  • Speed Controllable

What it is best used for

High volume ducted extract or supply on 400mm duct in factories, industrial units, warehousing, commercial kitchens and large office floors. At 100 Pa it moves 4090 m³/h, and it holds 2390 m³/h even at 500 Pa, which suits systems with filters, heater batteries and long runs.

At 64 kg it needs proper support and access; check the void or roof space against Elta's dimensional drawing first. It is not suitable for corrosive or explosive atmospheres, and the airstream must stay within -20°C to +60°C.

Why choose this over alternatives

This is the 400mm SSDL with rectangular spigots and terminal box. Pick this version when the fan connects to rectangular ductwork and you also want a pre-fitted terminal box for a quick, tidy electrical connection. The fan, motor and performance are identical across the four versions, so the choice is only about duct shape and wiring. The same size is also available as Elta SSDL400-1EC (circular spigots), Elta SSDL400-1EC-T (circular spigots with terminal box) and Elta SSDL400-1EC-R (rectangular spigots).

It shares its casing size with the Elta SSDL500-1EC-RT. The 500 moves more at low and medium pressure (5184 against 4090 m³/h at 100 Pa), but above about 400 Pa the 400 pulls ahead and gives 2390 m³/h at 500 Pa against 2192, so it is the better single phase choice for a high resistance system.

Installation notes

  • Mount it at any angle, indoors or outside, on drop rods or Elta's SEL anti-vibration mounts (upright or inverted), make sure it is adequately supported, and leave access for maintenance.
  • The inlet and outlet are rectangular spigots for rectangular ductwork. Check the spigot sizes on Elta's dimensional drawing before fabricating the duct connections.
  • A terminal box is pre-fitted to one side; tell us which side when ordering. Elta's drawing shows it adds 74mm to dimension B, so allow for that in tight voids.
  • Speed is set on the built-in commissioning potentiometer. To use an external potentiometer or a 0-10V BMS signal, remove the jumper link and connect to ST1; the commissioning setting then caps the maximum speed.
  • Disconnect the fan before any insulation resistance testing. Elta warn this can damage the EC electronics and is not covered by warranty.

You'll also need

Browse more commercial box fans, inline duct fans or Elta fans, or call us for help choosing the right fan.

Specifications

Model SSDL400-1EC-RT
Type Centrifugal box fan, rectangular spigots, terminal box
Size 400mm (rectangular spigots)
Max airflow 4414 m³/h
Static pressure 500 Pa
Motor Single phase EC, 220-240V 50/60Hz, 1620 rpm
Power 754 W at best efficiency point (5.19 A peak)
Noise 58 dB(A) inlet, 60 dB(A) outlet, 43 dB(A) breakout at 3m
IP rating IP44 motor
Warranty 1 Year Manufacturer
Airflow at 100 Pa 4090 m³/h
Airflow at 200 Pa 3722 m³/h
Airflow at 500 Pa 2390 m³/h
Spigots Rectangular inlet and outlet
Electrical connection Pre-fitted terminal box
Speed control Built-in commissioning potentiometer, 0-10V or external potentiometer input
Overall efficiency 50.0% at best efficiency point
SFP at 100 Pa 0.66 W/(L/s)
Casing 1.2mm galvanised mild steel, acoustically lined
Operating temperature -20°C to +60°C, up to 90% RH
Weight 64 kg
Wiring diagram 152-712
ErP Regulation (EU) 1253/2014, NRVU

Manuals & Guides

Product Description

The Elta SSDL400-1EC-RT is a 400mm Singleflow SSDL centrifugal box fan with rectangular inlet and outlet spigots and a pre-fitted terminal box. It moves up to 4414 m³/h in free air, 3722 m³/h at 200 Pa and still 2390 m³/h at 500 Pa, the highest pressure in Elta's published table.

A single phase EC external rotor motor (220-240V 50/60Hz) drives a backward curved impeller balanced to ISO1940-1, at up to 1620 rpm with an integrated commissioning control for setting speed. The 1.2mm galvanised steel casing is acoustically lined and suitable for external mounting, the IP44 motor has sealed for life bearings and runs in air from -20°C to +60°C, and Elta backs it with a 12 month warranty.

  • 1 Phase
  • EC Motor
  • Up to 4414 m³/h
  • Speed Controllable

What it is best used for

High volume ducted extract or supply on 400mm duct in factories, industrial units, warehousing, commercial kitchens and large office floors. At 100 Pa it moves 4090 m³/h, and it holds 2390 m³/h even at 500 Pa, which suits systems with filters, heater batteries and long runs.

At 64 kg it needs proper support and access; check the void or roof space against Elta's dimensional drawing first. It is not suitable for corrosive or explosive atmospheres, and the airstream must stay within -20°C to +60°C.

Why choose this over alternatives

This is the 400mm SSDL with rectangular spigots and terminal box. Pick this version when the fan connects to rectangular ductwork and you also want a pre-fitted terminal box for a quick, tidy electrical connection. The fan, motor and performance are identical across the four versions, so the choice is only about duct shape and wiring. The same size is also available as Elta SSDL400-1EC (circular spigots), Elta SSDL400-1EC-T (circular spigots with terminal box) and Elta SSDL400-1EC-R (rectangular spigots).

It shares its casing size with the Elta SSDL500-1EC-RT. The 500 moves more at low and medium pressure (5184 against 4090 m³/h at 100 Pa), but above about 400 Pa the 400 pulls ahead and gives 2390 m³/h at 500 Pa against 2192, so it is the better single phase choice for a high resistance system.

Installation notes

  • Mount it at any angle, indoors or outside, on drop rods or Elta's SEL anti-vibration mounts (upright or inverted), make sure it is adequately supported, and leave access for maintenance.
  • The inlet and outlet are rectangular spigots for rectangular ductwork. Check the spigot sizes on Elta's dimensional drawing before fabricating the duct connections.
  • A terminal box is pre-fitted to one side; tell us which side when ordering. Elta's drawing shows it adds 74mm to dimension B, so allow for that in tight voids.
  • Speed is set on the built-in commissioning potentiometer. To use an external potentiometer or a 0-10V BMS signal, remove the jumper link and connect to ST1; the commissioning setting then caps the maximum speed.
  • Disconnect the fan before any insulation resistance testing. Elta warn this can damage the EC electronics and is not covered by warranty.

You'll also need

Browse more commercial box fans, inline duct fans or Elta fans, or call us for help choosing the right fan.

Specifications

Model SSDL400-1EC-RT
Type Centrifugal box fan, rectangular spigots, terminal box
Size 400mm (rectangular spigots)
Max airflow 4414 m³/h
Static pressure 500 Pa
Motor Single phase EC, 220-240V 50/60Hz, 1620 rpm
Power 754 W at best efficiency point (5.19 A peak)
Noise 58 dB(A) inlet, 60 dB(A) outlet, 43 dB(A) breakout at 3m
IP rating IP44 motor
Warranty 1 Year Manufacturer
Airflow at 100 Pa 4090 m³/h
Airflow at 200 Pa 3722 m³/h
Airflow at 500 Pa 2390 m³/h
Spigots Rectangular inlet and outlet
Electrical connection Pre-fitted terminal box
Speed control Built-in commissioning potentiometer, 0-10V or external potentiometer input
Overall efficiency 50.0% at best efficiency point
SFP at 100 Pa 0.66 W/(L/s)
Casing 1.2mm galvanised mild steel, acoustically lined
Operating temperature -20°C to +60°C, up to 90% RH
Weight 64 kg
Wiring diagram 152-712
ErP Regulation (EU) 1253/2014, NRVU

Manuals & Guides

Delivery & Returns

Our Price Match Promise

Payment Methods

American Express Apple Pay Diners Club Discover Google Pay Maestro Mastercard PayPal Shop Pay Union Pay Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

What is the difference between the SSDL400-1EC, -R, -T and -RT?

The -RT has rectangular spigots plus a pre-fitted terminal box. The plain SSDL400-1EC has circular spigots and no terminal box, -T is circular with a terminal box and -R is rectangular without one. Performance is the same on all four.

How much air does the SSDL400-1EC-RT move?

Up to 4414 m³/h in free air at full speed, 4090 m³/h at 100 Pa, 3722 m³/h at 200 Pa and 2390 m³/h at 500 Pa.

How do I control the speed?

The built-in commissioning potentiometer sets a single speed or a maximum speed. For user control, Elta list the 149-POT-10-MI EC controller, or you can feed a 0-10V signal from a BMS after removing the jumper link.

Can it be mounted outside or on its side?

Yes. The SSDL is suitable for external mounting and can be mounted at any angle. The motor is IP44 and the fan is rated for air from -20°C to +60°C, up to 90% relative humidity.

How noisy is it?

At full speed Elta quote 58 dB(A) at the inlet, 60 dB(A) at the outlet and 43 dB(A) breakout at 3m. The casing is acoustically lined, and 068-0400-JF spigot silencers from 300 to 1200mm long are available to order.

What power supply does it need?

A single phase 220 to 240V 50/60Hz supply. Peak current is 5.19 A, and it uses Elta wiring diagram 152-712.