Elta SSDL200-1EC-RT Singleflow Centrifugal Box Fan Single Phase EC - 200mm (rectangular spigots and terminal box)
Suggested products
Free 14 day returns
Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.
Why choose eFans?
- Bulk pricing available
- Free help and advice
- Fast quotes, usually within the hour
- Huge range with next-day delivery
- Credit accounts available
Delivery and Warranty
Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days.
£7.95
Next Working Day Delivery
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays)
£15.95
Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95
Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95
Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95
Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95
Product Details
Specifications
Product specifications
| Model | SSDL200-1EC-RT |
| Type | Centrifugal box fan, rectangular spigots, terminal box |
| Size | 200mm (rectangular spigots) |
| Max airflow | 1148 m³/h |
| Static pressure | 500 Pa |
| Motor | Single phase EC, 220-240V 50/60Hz, 2410 rpm |
| Power | 156 W at best efficiency point (1.15 A peak) |
| Noise | 54 dB(A) inlet, 55 dB(A) outlet, 39 dB(A) breakout at 3m |
| IP rating | IP44 motor |
| Warranty | 1 Year Manufacturer |
Summary
See more specification See less specification
The Elta SSDL200-1EC-RT is a 200mm Singleflow SSDL centrifugal box fan with rectangular inlet and outlet spigots and a pre-fitted terminal box. It moves up to 1148 m³/h in free air, 896 m³/h at 200 Pa and still 436 m³/h at 500 Pa, the highest pressure in Elta's published table.
A single phase EC external rotor motor (220-240V 50/60Hz) drives a backward curved impeller balanced to ISO1940-1, at up to 2410 rpm with an integrated commissioning control for setting speed. The 1.2mm galvanised steel casing is acoustically lined and suitable for external mounting, the IP44 motor has sealed for life bearings and runs in air from -20°C to +60°C, and Elta backs it with a 12 month warranty.
- 1 Phase
- EC Motor
- Up to 1148 m³/h
- Speed Controllable
What it is best used for
Ducted extract or supply on 200mm duct for toilet blocks, hotel bathroom risers, classrooms, libraries and open plan offices. At 100 Pa it moves 1026 m³/h, roughly 10 air changes an hour in a space of about 100 m³, and it still delivers 896 m³/h at 200 Pa for longer duct runs with grilles and bends.
It is not suitable for corrosive or explosive atmospheres, and the airstream must stay within -20°C to +60°C. Where ceiling void depth is tight, an inline mixed flow fan is more compact than a box fan.
Why choose this over alternatives
This is the 200mm SSDL with rectangular spigots and terminal box. Pick this version when the fan connects to rectangular ductwork and you also want a pre-fitted terminal box for a quick, tidy electrical connection. The fan, motor and performance are identical across the four versions, so the choice is only about duct shape and wiring. The same size is also available as Elta SSDL200-1EC (circular spigots), Elta SSDL200-1EC-T (circular spigots with terminal box) and Elta SSDL200-1EC-R (rectangular spigots).
The 200 has a lower specific fan power than any smaller SSDL (0.56 W/(L/s) at 100 Pa) and 48.9% overall efficiency. The Elta SSDL250-1EC-RT moves more at low pressure (1184 m³/h at 100 Pa against 1026), but at 500 Pa the two are level (428 against 436 m³/h), so on a high resistance system the 200 does the same job in a smaller, lighter casing.
Installation notes
- Mount it at any angle, indoors or outside, on drop rods or Elta's SEL anti-vibration mounts (upright or inverted), make sure it is adequately supported, and leave access for maintenance.
- The inlet and outlet are rectangular spigots for rectangular ductwork. Check the spigot sizes on Elta's dimensional drawing before fabricating the duct connections.
- A terminal box is pre-fitted to one side; tell us which side when ordering. Elta's drawing shows it adds 74mm to dimension B, so allow for that in tight voids.
- Speed is set on the built-in commissioning potentiometer. To use an external potentiometer or a 0-10V BMS signal, remove the jumper link and connect to ST1; the commissioning setting then caps the maximum speed.
- Disconnect the fan before any insulation resistance testing. Elta warn this can damage the EC electronics and is not covered by warranty.
You'll also need
- Elta EC electronic controller 149-POT-10-MI (the potentiometer controller Elta list for every SSDL size)
- Elta anti-vibration mounts 062-SEL03 available to order, ask us
Browse more commercial box fans, inline duct fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SSDL200-1EC-RT |
| Type | Centrifugal box fan, rectangular spigots, terminal box |
| Size | 200mm (rectangular spigots) |
| Max airflow | 1148 m³/h |
| Static pressure | 500 Pa |
| Motor | Single phase EC, 220-240V 50/60Hz, 2410 rpm |
| Power | 156 W at best efficiency point (1.15 A peak) |
| Noise | 54 dB(A) inlet, 55 dB(A) outlet, 39 dB(A) breakout at 3m |
| IP rating | IP44 motor |
| Warranty | 1 Year Manufacturer |
| Airflow at 100 Pa | 1026 m³/h |
| Airflow at 200 Pa | 896 m³/h |
| Airflow at 500 Pa | 436 m³/h |
| Spigots | Rectangular inlet and outlet |
| Electrical connection | Pre-fitted terminal box |
| Speed control | Built-in commissioning potentiometer, 0-10V or external potentiometer input |
| Overall efficiency | 48.9% at best efficiency point |
| SFP at 100 Pa | 0.56 W/(L/s) |
| Casing | 1.2mm galvanised mild steel, acoustically lined |
| Operating temperature | -20°C to +60°C, up to 90% RH |
| Weight | 18 kg |
| Wiring diagram | 152-712 |
| ErP | Regulation (EU) 1253/2014, NRVU |
Manuals & Guides
Product Description
The Elta SSDL200-1EC-RT is a 200mm Singleflow SSDL centrifugal box fan with rectangular inlet and outlet spigots and a pre-fitted terminal box. It moves up to 1148 m³/h in free air, 896 m³/h at 200 Pa and still 436 m³/h at 500 Pa, the highest pressure in Elta's published table.
A single phase EC external rotor motor (220-240V 50/60Hz) drives a backward curved impeller balanced to ISO1940-1, at up to 2410 rpm with an integrated commissioning control for setting speed. The 1.2mm galvanised steel casing is acoustically lined and suitable for external mounting, the IP44 motor has sealed for life bearings and runs in air from -20°C to +60°C, and Elta backs it with a 12 month warranty.
- 1 Phase
- EC Motor
- Up to 1148 m³/h
- Speed Controllable
What it is best used for
Ducted extract or supply on 200mm duct for toilet blocks, hotel bathroom risers, classrooms, libraries and open plan offices. At 100 Pa it moves 1026 m³/h, roughly 10 air changes an hour in a space of about 100 m³, and it still delivers 896 m³/h at 200 Pa for longer duct runs with grilles and bends.
It is not suitable for corrosive or explosive atmospheres, and the airstream must stay within -20°C to +60°C. Where ceiling void depth is tight, an inline mixed flow fan is more compact than a box fan.
Why choose this over alternatives
This is the 200mm SSDL with rectangular spigots and terminal box. Pick this version when the fan connects to rectangular ductwork and you also want a pre-fitted terminal box for a quick, tidy electrical connection. The fan, motor and performance are identical across the four versions, so the choice is only about duct shape and wiring. The same size is also available as Elta SSDL200-1EC (circular spigots), Elta SSDL200-1EC-T (circular spigots with terminal box) and Elta SSDL200-1EC-R (rectangular spigots).
The 200 has a lower specific fan power than any smaller SSDL (0.56 W/(L/s) at 100 Pa) and 48.9% overall efficiency. The Elta SSDL250-1EC-RT moves more at low pressure (1184 m³/h at 100 Pa against 1026), but at 500 Pa the two are level (428 against 436 m³/h), so on a high resistance system the 200 does the same job in a smaller, lighter casing.
Installation notes
- Mount it at any angle, indoors or outside, on drop rods or Elta's SEL anti-vibration mounts (upright or inverted), make sure it is adequately supported, and leave access for maintenance.
- The inlet and outlet are rectangular spigots for rectangular ductwork. Check the spigot sizes on Elta's dimensional drawing before fabricating the duct connections.
- A terminal box is pre-fitted to one side; tell us which side when ordering. Elta's drawing shows it adds 74mm to dimension B, so allow for that in tight voids.
- Speed is set on the built-in commissioning potentiometer. To use an external potentiometer or a 0-10V BMS signal, remove the jumper link and connect to ST1; the commissioning setting then caps the maximum speed.
- Disconnect the fan before any insulation resistance testing. Elta warn this can damage the EC electronics and is not covered by warranty.
You'll also need
- Elta EC electronic controller 149-POT-10-MI (the potentiometer controller Elta list for every SSDL size)
- Elta anti-vibration mounts 062-SEL03 available to order, ask us
Browse more commercial box fans, inline duct fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SSDL200-1EC-RT |
| Type | Centrifugal box fan, rectangular spigots, terminal box |
| Size | 200mm (rectangular spigots) |
| Max airflow | 1148 m³/h |
| Static pressure | 500 Pa |
| Motor | Single phase EC, 220-240V 50/60Hz, 2410 rpm |
| Power | 156 W at best efficiency point (1.15 A peak) |
| Noise | 54 dB(A) inlet, 55 dB(A) outlet, 39 dB(A) breakout at 3m |
| IP rating | IP44 motor |
| Warranty | 1 Year Manufacturer |
| Airflow at 100 Pa | 1026 m³/h |
| Airflow at 200 Pa | 896 m³/h |
| Airflow at 500 Pa | 436 m³/h |
| Spigots | Rectangular inlet and outlet |
| Electrical connection | Pre-fitted terminal box |
| Speed control | Built-in commissioning potentiometer, 0-10V or external potentiometer input |
| Overall efficiency | 48.9% at best efficiency point |
| SFP at 100 Pa | 0.56 W/(L/s) |
| Casing | 1.2mm galvanised mild steel, acoustically lined |
| Operating temperature | -20°C to +60°C, up to 90% RH |
| Weight | 18 kg |
| Wiring diagram | 152-712 |
| ErP | Regulation (EU) 1253/2014, NRVU |
Manuals & Guides
Delivery & Returns
Our Price Match Promise
Payment Methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
What is the difference between the SSDL200-1EC, -R, -T and -RT?
The -RT has rectangular spigots plus a pre-fitted terminal box. The plain SSDL200-1EC has circular spigots and no terminal box, -T is circular with a terminal box and -R is rectangular without one. Performance is the same on all four.
How much air does the SSDL200-1EC-RT move?
Up to 1148 m³/h in free air at full speed, 1026 m³/h at 100 Pa, 896 m³/h at 200 Pa and 436 m³/h at 500 Pa.
How do I control the speed?
The built-in commissioning potentiometer sets a single speed or a maximum speed. For user control, Elta list the 149-POT-10-MI EC controller, or you can feed a 0-10V signal from a BMS after removing the jumper link.
Can it be mounted outside or on its side?
Yes. The SSDL is suitable for external mounting and can be mounted at any angle. The motor is IP44 and the fan is rated for air from -20°C to +60°C, up to 90% relative humidity.
How noisy is it?
At full speed Elta quote 54 dB(A) at the inlet, 55 dB(A) at the outlet and 39 dB(A) breakout at 3m. The casing is acoustically lined, and 068-0200-JF spigot silencers from 300 to 1200mm long are available to order.
What power supply does it need?
A single phase 220 to 240V 50/60Hz supply. Peak current is 1.15 A, and it uses Elta wiring diagram 152-712.