Elta SLCX500/4-3AC Revolution ATEX Long Cased Axial Fan Three Phase AC - 500mm
Suggested products
Free 14 day returns
Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.
Why choose eFans?
- Bulk pricing available
- Free help and advice
- Fast quotes, usually within the hour
- Huge range with next-day delivery
- Credit accounts available
Delivery and Warranty
Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days.
£7.95
Next Working Day Delivery
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays)
£15.95
Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95
Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95
Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95
Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95
Product Details
Specifications
Product specifications
| Model | SLCX500/4-3AC |
| Type | ATEX long cased axial fan, duct mounted |
| Diameter | 500mm |
| Max airflow | 9605 m³/h |
| Static pressure | 200 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 4 pole, 1380 rpm |
| Power | 1.1 kW (2.70 A peak) |
| Noise | 62 dB(A) inlet, 59 dB(A) outlet at 3m |
| ATEX marking | Ex h IIB+H2 T4 Gb |
| Warranty | 1 Year Manufacturer |
Summary
See more specification See less specification
The Elta SLCX500/4-3AC is a 500mm ATEX rated long cased axial fan from the Elta Revolution SLCX range, built for duct mounting in hazardous areas. It moves up to 9605 m³/h at free air and still delivers 6048 m³/h at 200 Pa, driven by a 1.1 kW 4 pole three phase motor running at 1380 rpm.
Elta mark the SLCX to Ex h IIB+H2 T4 Gb, classified for constructional safety under the 2014/34/EU directive. The casing is heavy gauge sheet steel, roll formed, welded and dip galvanised after fabrication, and the adjustable pitch aerofoil impeller has carbon filled anti-static blades on a die cast aluminium hub. It is fixed speed, direct on line, and Elta give a 12 month warranty.
- 3 Phase
- AC Motor
- Up to 9605 m³/h
- Fixed Speed
What it is best used for
Larger area ventilation in classified spaces with a moderate duct run: big battery charging rooms, wet wells and screen houses at water and sewage treatment works, chemical and solvent warehouses. It moves 9605 m³/h free air and 8341 m³/h at 100 Pa.
Its curve ends at 200 Pa. For higher resistance in the same 500mm duct use the Elta SLCX500/2-3AC or Elta SLCX500/2B-3AC, both rated to 500 Pa. It is not suitable for Zone 0, and the marking is for gas atmospheres only, so ask us before specifying it for a combustible dust zone. Zone classification is the responsibility of the installer or site duty holder: check the Ex h IIB+H2 T4 Gb marking against your hazardous area classification before ordering.
Why choose this over alternatives
Choose the SLCX only where the area is classified as hazardous. Its Ex h IIB+H2 T4 Gb marking, anti-static impeller blades and ATEX build are what you are paying for; the standard Elta SLC500 three phase is the non-ATEX version of a similar size for ordinary ventilation and costs considerably less, but must never be used in a zoned area.
It is the quietest 500mm option at 62 dB(A) inlet and 59 dB(A) outlet at 3m, using half the motor power of the 2 pole Elta SLCX500/2-3AC. If you need more volume at low pressure, the Elta SLCX560/4-3AC moves 13460 m³/h.
Installation notes
- Electrical installation must comply with BS7671 and EN60079-0 and be carried out by competent persons. Provide a means of electrical isolation in the fixed wiring and wire to diagram 152-612 through the M20 cable entry, with the M6 earth stud bonded.
- The fan can be mounted at any angle. Seal all flanges with an oil and diesel resistant silicone sealant, and fix to the 585mm flange using the 12 holes of 12mm diameter on a 560mm PCD.
- Elta state the zone inside and outside the fan can differ by no more than one zone (for example Zone 1 inside, Zone 2 outside), except when fitted with a flexible duct connection, where there is no zone separation. It is not suitable for Zone 0.
- It is fixed speed, direct on line. Elta must be consulted before any speed controller or inverter is used, and the controller in the ancillary pack is not ATEX rated and must be mounted outside the hazardous area.
- At start up check rotation, airflow direction and that motor current does not exceed the nameplate. Inspect AV mounts and earth bonding every 6 months, and check impeller tip clearance every 26,000 hours or 3 years.
You'll also need
- Elta matching flanges 500mm (061B-0500) sold each, one per duct connection
- Elta ancillary pack APK500/003 available to order, ask us. Its controller is not ATEX rated and must be mounted outside the hazardous area.
- Elta AV mounts 062-003 available to order, ask us
- Elta impeller side guard 078C-0500-C available to order, ask us. Guarding is not included with the fan.
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SLCX500/4-3AC |
| Type | ATEX long cased axial fan, duct mounted |
| Diameter | 500mm |
| Max airflow | 9605 m³/h |
| Static pressure | 200 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 4 pole, 1380 rpm |
| Power | 1.1 kW (2.70 A peak) |
| Noise | 62 dB(A) inlet, 59 dB(A) outlet at 3m |
| ATEX marking | Ex h IIB+H2 T4 Gb |
| Warranty | 1 Year Manufacturer |
| Airflow at 100 Pa | 8341 m³/h |
| Airflow at 200 Pa | 6048 m³/h |
| Starting current | 11.10 A, direct on line |
| Speed control | Fixed speed, consult Elta before using a controller or inverter |
| Directive | 2014/34/EU, not suitable for Zone 0 |
| Ambient temperature | minus 20°C up to 40°C |
| Impeller | Adjustable pitch aerofoil, carbon filled anti-static blades, LM24 aluminium hub, balanced to ISO 14694 G6.3 |
| Casing | Heavy gauge steel, dip galvanised to BS EN ISO 1461 |
| Casing length | 450mm |
| Flange | 585mm outside diameter, 12 holes 12mm diameter on 560mm PCD |
| Cable entry | M20, terminal box on casing |
| Wiring diagram | 152-612 |
| Weight | 47 kg |
Manuals & Guides
Product Description
The Elta SLCX500/4-3AC is a 500mm ATEX rated long cased axial fan from the Elta Revolution SLCX range, built for duct mounting in hazardous areas. It moves up to 9605 m³/h at free air and still delivers 6048 m³/h at 200 Pa, driven by a 1.1 kW 4 pole three phase motor running at 1380 rpm.
Elta mark the SLCX to Ex h IIB+H2 T4 Gb, classified for constructional safety under the 2014/34/EU directive. The casing is heavy gauge sheet steel, roll formed, welded and dip galvanised after fabrication, and the adjustable pitch aerofoil impeller has carbon filled anti-static blades on a die cast aluminium hub. It is fixed speed, direct on line, and Elta give a 12 month warranty.
- 3 Phase
- AC Motor
- Up to 9605 m³/h
- Fixed Speed
What it is best used for
Larger area ventilation in classified spaces with a moderate duct run: big battery charging rooms, wet wells and screen houses at water and sewage treatment works, chemical and solvent warehouses. It moves 9605 m³/h free air and 8341 m³/h at 100 Pa.
Its curve ends at 200 Pa. For higher resistance in the same 500mm duct use the Elta SLCX500/2-3AC or Elta SLCX500/2B-3AC, both rated to 500 Pa. It is not suitable for Zone 0, and the marking is for gas atmospheres only, so ask us before specifying it for a combustible dust zone. Zone classification is the responsibility of the installer or site duty holder: check the Ex h IIB+H2 T4 Gb marking against your hazardous area classification before ordering.
Why choose this over alternatives
Choose the SLCX only where the area is classified as hazardous. Its Ex h IIB+H2 T4 Gb marking, anti-static impeller blades and ATEX build are what you are paying for; the standard Elta SLC500 three phase is the non-ATEX version of a similar size for ordinary ventilation and costs considerably less, but must never be used in a zoned area.
It is the quietest 500mm option at 62 dB(A) inlet and 59 dB(A) outlet at 3m, using half the motor power of the 2 pole Elta SLCX500/2-3AC. If you need more volume at low pressure, the Elta SLCX560/4-3AC moves 13460 m³/h.
Installation notes
- Electrical installation must comply with BS7671 and EN60079-0 and be carried out by competent persons. Provide a means of electrical isolation in the fixed wiring and wire to diagram 152-612 through the M20 cable entry, with the M6 earth stud bonded.
- The fan can be mounted at any angle. Seal all flanges with an oil and diesel resistant silicone sealant, and fix to the 585mm flange using the 12 holes of 12mm diameter on a 560mm PCD.
- Elta state the zone inside and outside the fan can differ by no more than one zone (for example Zone 1 inside, Zone 2 outside), except when fitted with a flexible duct connection, where there is no zone separation. It is not suitable for Zone 0.
- It is fixed speed, direct on line. Elta must be consulted before any speed controller or inverter is used, and the controller in the ancillary pack is not ATEX rated and must be mounted outside the hazardous area.
- At start up check rotation, airflow direction and that motor current does not exceed the nameplate. Inspect AV mounts and earth bonding every 6 months, and check impeller tip clearance every 26,000 hours or 3 years.
You'll also need
- Elta matching flanges 500mm (061B-0500) sold each, one per duct connection
- Elta ancillary pack APK500/003 available to order, ask us. Its controller is not ATEX rated and must be mounted outside the hazardous area.
- Elta AV mounts 062-003 available to order, ask us
- Elta impeller side guard 078C-0500-C available to order, ask us. Guarding is not included with the fan.
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SLCX500/4-3AC |
| Type | ATEX long cased axial fan, duct mounted |
| Diameter | 500mm |
| Max airflow | 9605 m³/h |
| Static pressure | 200 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 4 pole, 1380 rpm |
| Power | 1.1 kW (2.70 A peak) |
| Noise | 62 dB(A) inlet, 59 dB(A) outlet at 3m |
| ATEX marking | Ex h IIB+H2 T4 Gb |
| Warranty | 1 Year Manufacturer |
| Airflow at 100 Pa | 8341 m³/h |
| Airflow at 200 Pa | 6048 m³/h |
| Starting current | 11.10 A, direct on line |
| Speed control | Fixed speed, consult Elta before using a controller or inverter |
| Directive | 2014/34/EU, not suitable for Zone 0 |
| Ambient temperature | minus 20°C up to 40°C |
| Impeller | Adjustable pitch aerofoil, carbon filled anti-static blades, LM24 aluminium hub, balanced to ISO 14694 G6.3 |
| Casing | Heavy gauge steel, dip galvanised to BS EN ISO 1461 |
| Casing length | 450mm |
| Flange | 585mm outside diameter, 12 holes 12mm diameter on 560mm PCD |
| Cable entry | M20, terminal box on casing |
| Wiring diagram | 152-612 |
| Weight | 47 kg |
Manuals & Guides
Delivery & Returns
Our Price Match Promise
Payment Methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
What ATEX zones can the Elta SLCX500/4-3AC be used in?
It is marked Ex h IIB+H2 T4 Gb. Elta state it is not suitable for Zone 0, and the zone inside and outside the fan can differ by no more than one zone, for example Zone 1 inside and Zone 2 outside. The installer or site duty holder is responsible for zone classification, so check the marking on the label and Certificate of Conformity against your hazardous area drawing.
Which gases is the SLCX500/4-3AC certified for?
Gas group IIB plus hydrogen (IIB+H2) with temperature class T4 and equipment protection level Gb. The marking covers gas atmospheres only, so ask us before using it in a combustible dust zone.
How much air does the SLCX500/4-3AC move?
Up to 9605 m³/h (2.668 m³/s) at free air, 8341 m³/h at 100 Pa and 6048 m³/h at 200 Pa, the highest pressure in the Elta performance table for this model.
Can I use a speed controller with it?
It is supplied as a fixed speed, direct on line fan. Elta must be consulted before a speed controller or inverter is used, and the controller in the Elta ancillary pack is not ATEX rated and must be mounted outside the hazardous area.
What size flanges and duct does the SLCX500/4-3AC need?
It fits a 500mm duct. The flange is 585mm across with 12 holes of 12mm diameter on a 560mm PCD, the casing is 450mm long and the fan weighs 47 kg.
Can it be mounted vertically?
Yes. Elta allow mounting at any angle, for extract or supply, as long as the fan is properly supported. Wiring diagram 152-612 shows connections for both A and B flow directions, so check rotation and airflow direction at start up.