Elta SLC710/4A-3AC Revolution Long Cased Axial Fan Three Phase AC - 710mm
Suggested products
Free 14 day returns
Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.
Why choose eFans?
- Bulk pricing available
- Free help and advice
- Fast quotes, usually within the hour
- Huge range with next-day delivery
- Credit accounts available
Delivery and Warranty
Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days.
£7.95
Next Working Day Delivery
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays)
£15.95
Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95
Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95
Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95
Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95
Product Details
Specifications
Product specifications
| Model | SLC710/4A-3AC |
| Type | Long cased axial fan |
| Diameter | 710mm |
| Max airflow | 26852 m³/h |
| Static pressure | 300 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 4 pole, 1440 rpm |
| Power | 3.37 kW (6.17 A) |
| Noise | 71 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
Summary
See more specification See less specification
The Elta SLC710/4A-3AC is a 710mm Revolution long cased axial fan and the smaller motor of the two four pole 710mm models. It moves up to 26852 m³/h at free air and 17543 m³/h against 300 Pa, from a 4 pole three phase AC motor running at 1440 rpm.
The casing is heavy gauge steel, hot dip galvanised to BS EN ISO 1461 and suitable for external mounting, with a die cast aluminium aerofoil impeller. The motor is IP55 with sealed for life bearings, wired to an IP55 terminal box on the outside of the case. The IE2 motor is designed for use with a frequency inverter. Elta give a 12 month warranty.
- 3 Phase
- AC Motor
- Up to 26852 m³/h
- Speed Controllable
What it is best used for
Very large air volumes on three phase: warehouse and distribution centre ventilation, factory general extract, large sports halls, livestock buildings and plant cooling, ducted up to 300 Pa. It moves 26852 m³/h at free air, about 10 air changes an hour in roughly 2690 m³.
It is 70 kg and 71 dB(A) at 3m, and Elta list only a three phase input inverter for it. Plan supports, isolation and attenuation from the start.
Why choose this over alternatives
The Elta SLC710/4B-3AC in the same casing adds about 1950 m³/h at free air and about 3985 m³/h at 300 Pa, for 4.46 kW against 3.37 kW. Choose the 4A when its curve covers your duty, as it is cheaper to run.
If you do not need 710mm, the Elta SLC630/4B-3AC moves 20243 m³/h on 2.24 kW.
Installation notes
- Mount at any angle, horizontally in a duct run or vertically, but make sure the fan is adequately supported: it weighs 70 kg. AV mounts and mounting feet are available from Elta.
- The flanges are 795mm outside diameter with 16 holes of 12mm on a 770mm PCD. Use Elta matching flanges and flexible connectors to join it to ductwork.
- Fit a local isolator, and protect the motor with a starter or controller that has overload protection; fuses and breakers only give short circuit protection. Do not use the isolator for day to day on and off control.
- Wire to diagram 152-600 (star connected, 380-415V three phase). Check rotation and airflow direction at first start and that the running current does not exceed the nameplate.
- Not suitable for corrosive or explosive atmospheres. Inspect and clean the impeller, motor and guards at least every 12 months.
You'll also need
- Elta matching flanges 061B-0710 (sold each, one per ducted side; available to order, ask us)
- Eltadrive 149-ODE3-24400-3KA4B inverter for a three phase supply (available to order, ask us)
- Elta APK710/004 ancillary pack (flexible connections, matching flanges, AV mounts and mounting feet in one code; available to order, ask us)
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SLC710/4A-3AC |
| Type | Long cased axial fan |
| Diameter | 710mm |
| Max airflow | 26852 m³/h |
| Static pressure | 300 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 4 pole, 1440 rpm |
| Power | 3.37 kW (6.17 A) |
| Noise | 71 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
| Airflow at 300 Pa | 17543 m³/h |
| Case length (dimension C) | 450mm |
| Flange | 795mm OD, 16 holes 12mm on 770mm PCD |
| Weight | 70 kg |
| Overall efficiency | 43.9% (FMEG N 46) |
| Motor efficiency | IE2 |
| Motor connection | Star (Y) |
| Wiring diagram | 152-600 |
| Ambient temperature | -20°C to +54°C |
| Casing | Hot dip galvanised steel |
Manuals & Guides
Product Description
The Elta SLC710/4A-3AC is a 710mm Revolution long cased axial fan and the smaller motor of the two four pole 710mm models. It moves up to 26852 m³/h at free air and 17543 m³/h against 300 Pa, from a 4 pole three phase AC motor running at 1440 rpm.
The casing is heavy gauge steel, hot dip galvanised to BS EN ISO 1461 and suitable for external mounting, with a die cast aluminium aerofoil impeller. The motor is IP55 with sealed for life bearings, wired to an IP55 terminal box on the outside of the case. The IE2 motor is designed for use with a frequency inverter. Elta give a 12 month warranty.
- 3 Phase
- AC Motor
- Up to 26852 m³/h
- Speed Controllable
What it is best used for
Very large air volumes on three phase: warehouse and distribution centre ventilation, factory general extract, large sports halls, livestock buildings and plant cooling, ducted up to 300 Pa. It moves 26852 m³/h at free air, about 10 air changes an hour in roughly 2690 m³.
It is 70 kg and 71 dB(A) at 3m, and Elta list only a three phase input inverter for it. Plan supports, isolation and attenuation from the start.
Why choose this over alternatives
The Elta SLC710/4B-3AC in the same casing adds about 1950 m³/h at free air and about 3985 m³/h at 300 Pa, for 4.46 kW against 3.37 kW. Choose the 4A when its curve covers your duty, as it is cheaper to run.
If you do not need 710mm, the Elta SLC630/4B-3AC moves 20243 m³/h on 2.24 kW.
Installation notes
- Mount at any angle, horizontally in a duct run or vertically, but make sure the fan is adequately supported: it weighs 70 kg. AV mounts and mounting feet are available from Elta.
- The flanges are 795mm outside diameter with 16 holes of 12mm on a 770mm PCD. Use Elta matching flanges and flexible connectors to join it to ductwork.
- Fit a local isolator, and protect the motor with a starter or controller that has overload protection; fuses and breakers only give short circuit protection. Do not use the isolator for day to day on and off control.
- Wire to diagram 152-600 (star connected, 380-415V three phase). Check rotation and airflow direction at first start and that the running current does not exceed the nameplate.
- Not suitable for corrosive or explosive atmospheres. Inspect and clean the impeller, motor and guards at least every 12 months.
You'll also need
- Elta matching flanges 061B-0710 (sold each, one per ducted side; available to order, ask us)
- Eltadrive 149-ODE3-24400-3KA4B inverter for a three phase supply (available to order, ask us)
- Elta APK710/004 ancillary pack (flexible connections, matching flanges, AV mounts and mounting feet in one code; available to order, ask us)
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SLC710/4A-3AC |
| Type | Long cased axial fan |
| Diameter | 710mm |
| Max airflow | 26852 m³/h |
| Static pressure | 300 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 4 pole, 1440 rpm |
| Power | 3.37 kW (6.17 A) |
| Noise | 71 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
| Airflow at 300 Pa | 17543 m³/h |
| Case length (dimension C) | 450mm |
| Flange | 795mm OD, 16 holes 12mm on 770mm PCD |
| Weight | 70 kg |
| Overall efficiency | 43.9% (FMEG N 46) |
| Motor efficiency | IE2 |
| Motor connection | Star (Y) |
| Wiring diagram | 152-600 |
| Ambient temperature | -20°C to +54°C |
| Casing | Hot dip galvanised steel |
Manuals & Guides
Delivery & Returns
Our Price Match Promise
Payment Methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
What size duct does the Elta SLC710/4A-3AC fit?
It is a 710mm fan with 710mm inside the casing. The flanges are 795mm outside diameter with 16 holes of 12mm on a 770mm PCD, and the case is 450mm long (dimension C).
How much air does it move?
Up to 26852 m³/h (7.459 m³/s) at free air, falling to 17543 m³/h at 300 Pa, the highest pressure in Elta's table for this model.
Is the SLC710/4A-3AC single or three phase?
Three phase, 380-415V 50Hz, star connected. Peak current is 6.17 A.
Can I control the speed of the SLC710/4A-3AC?
Yes, with a three phase frequency inverter. Elta list the Eltadrive 149-ODE3-24400-3KA4B. No single phase input drive or transformer controller is listed for this model.
How noisy is it?
71 dB(A) at 3m in free field, per Elta's data. Elta offer podded and unpodded silencers in 1D and 2D lengths for this size if you need it quieter.
Can it be mounted outside or vertically?
Yes. The galvanised casing is suitable for external mounting as standard and the fan can be mounted at any angle. For explosive atmospheres you need the ATEX rated Elta SLCX range instead.