Elta SLC560/4B-1AC Revolution Long Cased Axial Fan Single Phase AC - 560mm
Suggested products
Free 14 day returns
Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.
Why choose eFans?
- Bulk pricing available
- Free help and advice
- Fast quotes, usually within the hour
- Huge range with next-day delivery
- Credit accounts available
Delivery and Warranty
Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days.
£7.95
Next Working Day Delivery
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays)
£15.95
Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95
Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95
Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95
Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95
Product Details
Specifications
Product specifications
| Model | SLC560/4B-1AC |
| Type | Long cased axial fan |
| Diameter | 560mm |
| Max airflow | 11804 m³/h |
| Static pressure | 200 Pa |
| Motor | Single phase AC, 220-240V 50Hz, 4 pole, 1460 rpm |
| Power | 1.225 kW (5.5 A) |
| Noise | 60 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
Summary
See more specification See less specification
The Elta SLC560/4B-1AC is a 560mm Revolution long cased axial fan and the larger motor single phase model at 560mm. It moves up to 11804 m³/h at free air and 8950 m³/h against 200 Pa, from a 4 pole single phase AC motor running at 1460 rpm.
The casing is heavy gauge steel, hot dip galvanised to BS EN ISO 1461 and suitable for external mounting, with a die cast aluminium aerofoil impeller. The motor is IP55 with sealed for life bearings, wired to an IP55 terminal box on the outside of the case. Speed control is by a 149-TC116 transformer controller. Elta give a 12 month warranty.
- 1 Phase
- AC Motor
- Up to 11804 m³/h
- Speed Controllable
What it is best used for
Higher airflow general ventilation where only single phase is available: sports halls, agricultural buildings, workshops, warehouses and school halls, wall mounted or on duct runs up to 200 Pa. It moves 11804 m³/h at free air, roughly 10 air changes an hour in about 1180 m³.
It draws up to 5.5 A, so check the circuit. Its table stops at 200 Pa (8950 m³/h), so it is not suited to long filtered systems.
Why choose this over alternatives
Against the Elta SLC560/4A-1AC (10922 m³/h free air, 7204 m³/h at 200 Pa), the 4B holds noticeably more air under load: 8950 m³/h at 200 Pa, for 1.225 kW instead of 0.94 kW.
If you want fine speed control on single phase, the Elta SLC560-1EC EC model is an alternative. With three phase available, the Elta SLC560/4B-3AC goes to 250 Pa.
Installation notes
- Mount at any angle, horizontally in a duct run or vertically, but make sure the fan is adequately supported: it weighs 57 kg. AV mounts and mounting feet are available from Elta.
- The flanges are 645mm outside diameter with 12 holes of 12mm on a 620mm PCD. Use Elta matching flanges and flexible connectors to join it to ductwork.
- Fit a local isolator, and protect the motor with a starter or controller that has overload protection; fuses and breakers only give short circuit protection. Do not use the isolator for day to day on and off control.
- Wire to diagram 152-502 for 220-240V single phase. Check rotation and airflow direction at first start and that the running current does not exceed the nameplate.
- Not suitable for corrosive or explosive atmospheres. Inspect and clean the impeller, motor and guards at least every 12 months.
You'll also need
- Elta matching flanges 560mm (061B-0560) (sold each, one per ducted side)
- Elta 149-TC116 transformer speed controller (available to order, ask us)
- Elta APK560/003 ancillary pack (flexible connections, matching flanges, AV mounts and mounting feet in one code; available to order, ask us)
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SLC560/4B-1AC |
| Type | Long cased axial fan |
| Diameter | 560mm |
| Max airflow | 11804 m³/h |
| Static pressure | 200 Pa |
| Motor | Single phase AC, 220-240V 50Hz, 4 pole, 1460 rpm |
| Power | 1.225 kW (5.5 A) |
| Noise | 60 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
| Airflow at 200 Pa | 8950 m³/h |
| Case length (dimension C) | 450mm |
| Flange | 645mm OD, 12 holes 12mm on 620mm PCD |
| Weight | 57 kg |
| Overall efficiency | 40.3% (FMEG N 46) |
| Wiring diagram | 152-502 |
| Ambient temperature | -20°C to +54°C |
| Casing | Hot dip galvanised steel |
Manuals & Guides
Product Description
The Elta SLC560/4B-1AC is a 560mm Revolution long cased axial fan and the larger motor single phase model at 560mm. It moves up to 11804 m³/h at free air and 8950 m³/h against 200 Pa, from a 4 pole single phase AC motor running at 1460 rpm.
The casing is heavy gauge steel, hot dip galvanised to BS EN ISO 1461 and suitable for external mounting, with a die cast aluminium aerofoil impeller. The motor is IP55 with sealed for life bearings, wired to an IP55 terminal box on the outside of the case. Speed control is by a 149-TC116 transformer controller. Elta give a 12 month warranty.
- 1 Phase
- AC Motor
- Up to 11804 m³/h
- Speed Controllable
What it is best used for
Higher airflow general ventilation where only single phase is available: sports halls, agricultural buildings, workshops, warehouses and school halls, wall mounted or on duct runs up to 200 Pa. It moves 11804 m³/h at free air, roughly 10 air changes an hour in about 1180 m³.
It draws up to 5.5 A, so check the circuit. Its table stops at 200 Pa (8950 m³/h), so it is not suited to long filtered systems.
Why choose this over alternatives
Against the Elta SLC560/4A-1AC (10922 m³/h free air, 7204 m³/h at 200 Pa), the 4B holds noticeably more air under load: 8950 m³/h at 200 Pa, for 1.225 kW instead of 0.94 kW.
If you want fine speed control on single phase, the Elta SLC560-1EC EC model is an alternative. With three phase available, the Elta SLC560/4B-3AC goes to 250 Pa.
Installation notes
- Mount at any angle, horizontally in a duct run or vertically, but make sure the fan is adequately supported: it weighs 57 kg. AV mounts and mounting feet are available from Elta.
- The flanges are 645mm outside diameter with 12 holes of 12mm on a 620mm PCD. Use Elta matching flanges and flexible connectors to join it to ductwork.
- Fit a local isolator, and protect the motor with a starter or controller that has overload protection; fuses and breakers only give short circuit protection. Do not use the isolator for day to day on and off control.
- Wire to diagram 152-502 for 220-240V single phase. Check rotation and airflow direction at first start and that the running current does not exceed the nameplate.
- Not suitable for corrosive or explosive atmospheres. Inspect and clean the impeller, motor and guards at least every 12 months.
You'll also need
- Elta matching flanges 560mm (061B-0560) (sold each, one per ducted side)
- Elta 149-TC116 transformer speed controller (available to order, ask us)
- Elta APK560/003 ancillary pack (flexible connections, matching flanges, AV mounts and mounting feet in one code; available to order, ask us)
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SLC560/4B-1AC |
| Type | Long cased axial fan |
| Diameter | 560mm |
| Max airflow | 11804 m³/h |
| Static pressure | 200 Pa |
| Motor | Single phase AC, 220-240V 50Hz, 4 pole, 1460 rpm |
| Power | 1.225 kW (5.5 A) |
| Noise | 60 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
| Airflow at 200 Pa | 8950 m³/h |
| Case length (dimension C) | 450mm |
| Flange | 645mm OD, 12 holes 12mm on 620mm PCD |
| Weight | 57 kg |
| Overall efficiency | 40.3% (FMEG N 46) |
| Wiring diagram | 152-502 |
| Ambient temperature | -20°C to +54°C |
| Casing | Hot dip galvanised steel |
Manuals & Guides
Delivery & Returns
Our Price Match Promise
Payment Methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
What size duct does the Elta SLC560/4B-1AC fit?
It is a 560mm fan with 560mm inside the casing. The flanges are 645mm outside diameter with 12 holes of 12mm on a 620mm PCD, and the case is 450mm long (dimension C).
How much air does it move?
Up to 11804 m³/h (3.279 m³/s) at free air, falling to 8950 m³/h at 200 Pa, the highest pressure in Elta's table for this model.
Is the SLC560/4B-1AC single or three phase?
Single phase, 220-240V 50Hz. Peak current is 5.5 A.
Which speed controller does the SLC560/4B-1AC need?
Elta list the 149-TC116 single phase 5 step transformer controller for this model. We can supply it to order, so ask us.
How noisy is it?
60 dB(A) at 3m in free field, per Elta's data. Elta offer podded and unpodded silencers in 1D and 2D lengths for this size if you need it quieter.
Can it be mounted outside or vertically?
Yes. The galvanised casing is suitable for external mounting as standard and the fan can be mounted at any angle. For explosive atmospheres you need the ATEX rated Elta SLCX range instead.