Elta SLC500 Revolution Long Cased Axial Fan Single Phase AC - 500mm
Suggested products
Free 14 day returns
Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.
Why choose eFans?
- Bulk pricing available
- Free help and advice
- Fast quotes, usually within the hour
- Huge range with next-day delivery
- Credit accounts available
Delivery and Warranty
Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days.
£7.95
Next Working Day Delivery
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays)
£15.95
Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95
Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95
Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95
Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95
Product Details
Downloads
Specifications
Product specifications
| Model | SLC500/4A-1AC |
| Type | Long cased axial fan |
| Diameter | 500mm |
| Max airflow | 7427 m³/h |
| Static pressure | 150 Pa |
| Motor | Single phase AC, 220-240V 50Hz, 4 pole, 1460 rpm |
| Power | 483 W (2.09 A) |
| Noise | 53 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
Summary
See more specification See less specification
The Elta SLC500/4A-1AC is a 500mm Revolution long cased axial fan and the smaller motor single phase AC model at 500mm. It moves up to 7427 m³/h at free air and 4846 m³/h against 150 Pa, from a 4 pole single phase AC motor running at 1460 rpm.
The casing is heavy gauge steel, hot dip galvanised to BS EN ISO 1461 and suitable for external mounting, with a die cast aluminium aerofoil impeller. The motor is IP55 with sealed for life bearings, wired to an IP55 terminal box on the outside of the case. Elta list no speed controller for this model, so it runs at fixed speed. Elta give a 12 month warranty.
- 1 Phase
- AC Motor
- Up to 7427 m³/h
- Fixed Speed
What it is best used for
General ventilation on single phase at low to moderate pressure: sports halls, workshops, small warehouses, livestock and agricultural buildings, through the wall or ducted up to 150 Pa. It moves 7427 m³/h at free air on 0.483 kW and is quiet at 53 dB(A) at 3m.
At 150 Pa it is down to 4846 m³/h, so it is not for long filtered ductwork. Elta list no speed controller for this model, so plan on fixed speed; if you need control, the SLC500/4B-1AC (149-TC18) or the SLC500-1EC are the alternatives.
Why choose this over alternatives
The Elta SLC500/4B-1AC in the same 500mm size moves 9266 m³/h at free air and 6336 m³/h at 150 Pa on 0.702 kW, and it has a listed transformer controller. Choose the 4A when its curve covers the duty and fixed speed is fine, as it is cheaper to run.
For quiet variable speed on single phase, the Elta SLC500-1EC moves 8147 m³/h at full speed and reaches 200 Pa.
Installation notes
- Mount at any angle, horizontally in a duct run or vertically, and make sure the fan is adequately supported: it weighs 37 kg. AV mounts and mounting feet are available from Elta.
- The flanges are 585mm outside diameter with 12 holes of 12mm on a 560mm PCD. Use Elta matching flanges and flexible connectors to join it to ductwork.
- Fit a local isolator, and protect the motor with a starter or controller that has overload protection; fuses and breakers only give short circuit protection. Do not use the isolator for day to day on and off control.
- Wire to diagram 152-502 for 220-240V single phase. Check rotation and airflow direction at first start and that the running current does not exceed the nameplate.
- Not suitable for corrosive or explosive atmospheres. Inspect and clean the impeller, motor and guards at least every 12 months.
You'll also need
- Elta matching flanges 500mm (061B-0500) (sold each, one per ducted side)
- Elta APK500/003 ancillary pack (flexible connections, matching flanges, AV mounts and mounting feet in one code; available to order, ask us)
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SLC500/4A-1AC |
| Type | Long cased axial fan |
| Diameter | 500mm |
| Max airflow | 7427 m³/h |
| Static pressure | 150 Pa |
| Motor | Single phase AC, 220-240V 50Hz, 4 pole, 1460 rpm |
| Power | 483 W (2.09 A) |
| Noise | 53 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
| Airflow at 150 Pa | 4846 m³/h |
| Case length (dimension C) | 400mm |
| Flange | 585mm OD, 12 holes 12mm on 560mm PCD |
| Weight | 37 kg |
| Overall efficiency | 42.2% (FMEG N 50) |
| Wiring diagram | 152-502 |
| Ambient temperature | -20°C to +54°C |
| Casing | Hot dip galvanised steel |
Manuals & Guides
Product Description
The Elta SLC500/4A-1AC is a 500mm Revolution long cased axial fan and the smaller motor single phase AC model at 500mm. It moves up to 7427 m³/h at free air and 4846 m³/h against 150 Pa, from a 4 pole single phase AC motor running at 1460 rpm.
The casing is heavy gauge steel, hot dip galvanised to BS EN ISO 1461 and suitable for external mounting, with a die cast aluminium aerofoil impeller. The motor is IP55 with sealed for life bearings, wired to an IP55 terminal box on the outside of the case. Elta list no speed controller for this model, so it runs at fixed speed. Elta give a 12 month warranty.
- 1 Phase
- AC Motor
- Up to 7427 m³/h
- Fixed Speed
What it is best used for
General ventilation on single phase at low to moderate pressure: sports halls, workshops, small warehouses, livestock and agricultural buildings, through the wall or ducted up to 150 Pa. It moves 7427 m³/h at free air on 0.483 kW and is quiet at 53 dB(A) at 3m.
At 150 Pa it is down to 4846 m³/h, so it is not for long filtered ductwork. Elta list no speed controller for this model, so plan on fixed speed; if you need control, the SLC500/4B-1AC (149-TC18) or the SLC500-1EC are the alternatives.
Why choose this over alternatives
The Elta SLC500/4B-1AC in the same 500mm size moves 9266 m³/h at free air and 6336 m³/h at 150 Pa on 0.702 kW, and it has a listed transformer controller. Choose the 4A when its curve covers the duty and fixed speed is fine, as it is cheaper to run.
For quiet variable speed on single phase, the Elta SLC500-1EC moves 8147 m³/h at full speed and reaches 200 Pa.
Installation notes
- Mount at any angle, horizontally in a duct run or vertically, and make sure the fan is adequately supported: it weighs 37 kg. AV mounts and mounting feet are available from Elta.
- The flanges are 585mm outside diameter with 12 holes of 12mm on a 560mm PCD. Use Elta matching flanges and flexible connectors to join it to ductwork.
- Fit a local isolator, and protect the motor with a starter or controller that has overload protection; fuses and breakers only give short circuit protection. Do not use the isolator for day to day on and off control.
- Wire to diagram 152-502 for 220-240V single phase. Check rotation and airflow direction at first start and that the running current does not exceed the nameplate.
- Not suitable for corrosive or explosive atmospheres. Inspect and clean the impeller, motor and guards at least every 12 months.
You'll also need
- Elta matching flanges 500mm (061B-0500) (sold each, one per ducted side)
- Elta APK500/003 ancillary pack (flexible connections, matching flanges, AV mounts and mounting feet in one code; available to order, ask us)
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SLC500/4A-1AC |
| Type | Long cased axial fan |
| Diameter | 500mm |
| Max airflow | 7427 m³/h |
| Static pressure | 150 Pa |
| Motor | Single phase AC, 220-240V 50Hz, 4 pole, 1460 rpm |
| Power | 483 W (2.09 A) |
| Noise | 53 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
| Airflow at 150 Pa | 4846 m³/h |
| Case length (dimension C) | 400mm |
| Flange | 585mm OD, 12 holes 12mm on 560mm PCD |
| Weight | 37 kg |
| Overall efficiency | 42.2% (FMEG N 50) |
| Wiring diagram | 152-502 |
| Ambient temperature | -20°C to +54°C |
| Casing | Hot dip galvanised steel |
Manuals & Guides
Delivery & Returns
Our Price Match Promise
Payment Methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
What size duct does the Elta SLC500/4A-1AC fit?
It is a 500mm fan with 500mm inside the casing. The flanges are 585mm outside diameter with 12 holes of 12mm on a 560mm PCD, and the case is 400mm long.
How much air does it move?
Up to 7427 m³/h (2.063 m³/s) at free air, falling to 4846 m³/h at 150 Pa, the highest pressure in Elta's table for this model.
Is the SLC500/4A-1AC single or three phase?
Single phase, 220-240V 50Hz. Peak current is 2.09 A.
Can I control the speed of the SLC500/4A-1AC?
Elta's accessory table lists no speed controller for this model, so treat it as fixed speed. The SLC500/4B-1AC (with the 149-TC18) and the SLC500-1EC (0 to 10V) are the speed controllable alternatives at 500mm.
How noisy is it?
53 dB(A) at 3m in free field, per Elta's data. Elta offer podded and unpodded silencers in 1D and 2D lengths for this size if you need it quieter.
Can it be mounted outside or vertically?
Yes. The galvanised casing is suitable for external mounting as standard and the fan can be mounted at any angle. For explosive atmospheres you need the ATEX rated Elta SLCX range instead.