Elta SLC500/2A-3AC Revolution Long Cased Axial Fan Three Phase AC - 500mm
Suggested products
Free 14 day returns
Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.
Why choose eFans?
- Bulk pricing available
- Free help and advice
- Fast quotes, usually within the hour
- Huge range with next-day delivery
- Credit accounts available
Delivery and Warranty
Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days.
£7.95
Next Working Day Delivery
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays)
£15.95
Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95
Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95
Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95
Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95
Product Details
Specifications
Product specifications
| Model | SLC500/2A-3AC |
| Type | Long cased axial fan |
| Diameter | 500mm |
| Max airflow | 14580 m³/h |
| Static pressure | 500 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 2 pole, 2920 rpm |
| Power | 3.937 kW (7.06 A) |
| Noise | 70 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
Summary
See more specification See less specification
The Elta SLC500/2A-3AC is a 500mm Revolution long cased axial fan and the smaller of the two high pressure two pole 500mm models. It moves up to 14580 m³/h at free air and 11894 m³/h against 500 Pa, from a 2 pole three phase AC motor running at 2920 rpm.
The casing is heavy gauge steel, hot dip galvanised to BS EN ISO 1461 and suitable for external mounting, with a die cast aluminium aerofoil impeller. The motor is IP55 with sealed for life bearings, wired to an IP55 terminal box on the outside of the case. The IE2 motor is designed for use with a frequency inverter. Elta give a 12 month warranty.
- 3 Phase
- AC Motor
- Up to 14580 m³/h
- Speed Controllable
What it is best used for
Large ducted extract and supply systems that need serious pressure: factory and process extract, warehouse ventilation with long duct runs, kitchen canopy systems serving several canopies, and air handling or cooling duties. It holds 11894 m³/h at 500 Pa from 14580 m³/h at free air.
At 72 kg and 70 dB(A) at 3m it needs solid support and usually attenuation. It is a three phase only fan, and Elta list no single phase input inverter for it, so it is the wrong choice for a site without a three phase supply.
Why choose this over alternatives
The Elta SLC500/2B-3AC is the bigger motor version in the same casing, adding about 11% more airflow (16229 m³/h free air) for 5.192 kW instead of 3.937 kW. Pick the 2A when its curve covers your duty point, as it costs less to run.
If the system pressure is under 150 Pa, the four pole Elta SLC500/4A-3AC or Elta SLC500/4B-3AC will be much quieter and use a fraction of the power.
Installation notes
- Mount at any angle, horizontally in a duct run or vertically, but make sure the fan is adequately supported: it weighs 72 kg. AV mounts and mounting feet are available from Elta.
- The flanges are 585mm outside diameter with 12 holes of 12mm on a 560mm PCD. Use Elta matching flanges and flexible connectors to join it to ductwork.
- Fit a local isolator, and protect the motor with a starter or controller that has overload protection; fuses and breakers only give short circuit protection. Do not use the isolator for day to day on and off control.
- Wire to diagram 152-601 (delta connected, 380-415V three phase). Check rotation and airflow direction at first start and that the running current does not exceed the nameplate.
- Not suitable for corrosive or explosive atmospheres. Inspect and clean the impeller, motor and guards at least every 12 months.
You'll also need
- Elta matching flanges 500mm (061B-0500) (sold each, one per ducted side)
- Eltadrive 149-ODE3-24400-3KA4B inverter for a three phase supply (available to order, ask us)
- Elta APK500/003 ancillary pack (flexible connections, matching flanges, AV mounts and mounting feet in one code; available to order, ask us)
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SLC500/2A-3AC |
| Type | Long cased axial fan |
| Diameter | 500mm |
| Max airflow | 14580 m³/h |
| Static pressure | 500 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 2 pole, 2920 rpm |
| Power | 3.937 kW (7.06 A) |
| Noise | 70 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
| Airflow at 500 Pa | 11894 m³/h |
| Case length (dimension C) | 450mm |
| Flange | 585mm OD, 12 holes 12mm on 560mm PCD |
| Weight | 72 kg |
| Overall efficiency | 45.4% (FMEG N 47) |
| Motor efficiency | IE2 |
| Motor connection | Delta |
| Wiring diagram | 152-601 |
| Ambient temperature | -20°C to +54°C |
| Casing | Hot dip galvanised steel |
Manuals & Guides
Product Description
The Elta SLC500/2A-3AC is a 500mm Revolution long cased axial fan and the smaller of the two high pressure two pole 500mm models. It moves up to 14580 m³/h at free air and 11894 m³/h against 500 Pa, from a 2 pole three phase AC motor running at 2920 rpm.
The casing is heavy gauge steel, hot dip galvanised to BS EN ISO 1461 and suitable for external mounting, with a die cast aluminium aerofoil impeller. The motor is IP55 with sealed for life bearings, wired to an IP55 terminal box on the outside of the case. The IE2 motor is designed for use with a frequency inverter. Elta give a 12 month warranty.
- 3 Phase
- AC Motor
- Up to 14580 m³/h
- Speed Controllable
What it is best used for
Large ducted extract and supply systems that need serious pressure: factory and process extract, warehouse ventilation with long duct runs, kitchen canopy systems serving several canopies, and air handling or cooling duties. It holds 11894 m³/h at 500 Pa from 14580 m³/h at free air.
At 72 kg and 70 dB(A) at 3m it needs solid support and usually attenuation. It is a three phase only fan, and Elta list no single phase input inverter for it, so it is the wrong choice for a site without a three phase supply.
Why choose this over alternatives
The Elta SLC500/2B-3AC is the bigger motor version in the same casing, adding about 11% more airflow (16229 m³/h free air) for 5.192 kW instead of 3.937 kW. Pick the 2A when its curve covers your duty point, as it costs less to run.
If the system pressure is under 150 Pa, the four pole Elta SLC500/4A-3AC or Elta SLC500/4B-3AC will be much quieter and use a fraction of the power.
Installation notes
- Mount at any angle, horizontally in a duct run or vertically, but make sure the fan is adequately supported: it weighs 72 kg. AV mounts and mounting feet are available from Elta.
- The flanges are 585mm outside diameter with 12 holes of 12mm on a 560mm PCD. Use Elta matching flanges and flexible connectors to join it to ductwork.
- Fit a local isolator, and protect the motor with a starter or controller that has overload protection; fuses and breakers only give short circuit protection. Do not use the isolator for day to day on and off control.
- Wire to diagram 152-601 (delta connected, 380-415V three phase). Check rotation and airflow direction at first start and that the running current does not exceed the nameplate.
- Not suitable for corrosive or explosive atmospheres. Inspect and clean the impeller, motor and guards at least every 12 months.
You'll also need
- Elta matching flanges 500mm (061B-0500) (sold each, one per ducted side)
- Eltadrive 149-ODE3-24400-3KA4B inverter for a three phase supply (available to order, ask us)
- Elta APK500/003 ancillary pack (flexible connections, matching flanges, AV mounts and mounting feet in one code; available to order, ask us)
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SLC500/2A-3AC |
| Type | Long cased axial fan |
| Diameter | 500mm |
| Max airflow | 14580 m³/h |
| Static pressure | 500 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 2 pole, 2920 rpm |
| Power | 3.937 kW (7.06 A) |
| Noise | 70 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
| Airflow at 500 Pa | 11894 m³/h |
| Case length (dimension C) | 450mm |
| Flange | 585mm OD, 12 holes 12mm on 560mm PCD |
| Weight | 72 kg |
| Overall efficiency | 45.4% (FMEG N 47) |
| Motor efficiency | IE2 |
| Motor connection | Delta |
| Wiring diagram | 152-601 |
| Ambient temperature | -20°C to +54°C |
| Casing | Hot dip galvanised steel |
Manuals & Guides
Delivery & Returns
Our Price Match Promise
Payment Methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
What size duct does the Elta SLC500/2A-3AC fit?
It is a 500mm fan with 500mm inside the casing. The flanges are 585mm outside diameter with 12 holes of 12mm on a 560mm PCD, and the case is 450mm long (dimension C).
How much air does it move?
Up to 14580 m³/h (4.050 m³/s) at free air, falling to 11894 m³/h at 500 Pa, the highest pressure in Elta's table for this model.
Is the SLC500/2A-3AC single or three phase?
Three phase, 380-415V 50Hz, delta connected. Peak current is 7.06 A.
Can I control the speed of the SLC500/2A-3AC?
Yes, with a three phase frequency inverter. Elta list the Eltadrive 149-ODE3-24400-3KA4B. There is no single phase input drive or transformer controller listed for this model.
How noisy is it?
70 dB(A) at 3m in free field, per Elta's data. Elta offer podded and unpodded silencers in 1D and 2D lengths for this size if you need it quieter.
Can it be mounted outside or vertically?
Yes. The galvanised casing is suitable for external mounting as standard and the fan can be mounted at any angle. For explosive atmospheres you need the ATEX rated Elta SLCX range instead.