Elta SLC450/2-1AC Revolution Long Cased Axial Fan Single Phase AC - 450mm
Elta SLC450/2-1AC Revolution Long Cased Axial Fan Single Phase AC - 450mm
£1,625.99
SKU: SLC450/2-1AC

Elta SLC450/2-1AC Revolution Long Cased Axial Fan Single Phase AC - 450mm

1 Phase
AC Motor
Up to 10537 m³/h
Estimated delivery
Only 4 in stock
Not sure what you need? Email the teamhello@efans.co.uk
Free 14 day returns

Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.

Why choose eFans?
  • Bulk pricing available
  • Free help and advice
  • Fast quotes, usually within the hour
  • Huge range with next-day delivery
  • Credit accounts available
Delivery and Warranty

Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days. 
£7.95  

Next Working Day Delivery 
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays) 
£15.95 

Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95

Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95 

Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95

Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95 

Product Details

Specifications

Product specifications
Model SLC450/2-1AC
Type Long cased axial fan
Diameter 450mm
Max airflow 10537 m³/h
Static pressure 500 Pa
Motor Single phase AC, 220-240V 50Hz, 2 pole, 2815 rpm
Power 2.05 kW (8.8 A)
Noise 71 dB(A) at 3m
IP rating IP55
Warranty 1 Year Manufacturer

Summary

The Elta SLC450/2-1AC is a 450mm Revolution long cased axial fan and the only two pole single phase model at this size. It moves up to 10537 m³/h at free air and 6667 m³/h against 500 Pa, from a 2 pole single phase AC motor running at 2815 rpm.

The casing is heavy gauge steel, hot dip galvanised to BS EN ISO 1461 and suitable for external mounting, with a die cast aluminium aerofoil impeller. The motor is IP55 with sealed for life bearings, wired to an IP55 terminal box on the outside of the case. No speed controller is listed for this model, so it runs at fixed speed. Elta give a 12 month warranty.

See more specification See less specification

The Elta SLC450/2-1AC is a 450mm Revolution long cased axial fan and the only two pole single phase model at this size. It moves up to 10537 m³/h at free air and 6667 m³/h against 500 Pa, from a 2 pole single phase AC motor running at 2815 rpm.

The casing is heavy gauge steel, hot dip galvanised to BS EN ISO 1461 and suitable for external mounting, with a die cast aluminium aerofoil impeller. The motor is IP55 with sealed for life bearings, wired to an IP55 terminal box on the outside of the case. No speed controller is listed for this model, so it runs at fixed speed. Elta give a 12 month warranty.

  • 1 Phase
  • AC Motor
  • Up to 10537 m³/h
  • Fixed Speed

What it is best used for

High resistance duties where only a single phase supply is available: long ducted extract runs from workshops, farm buildings and plant rooms, systems with filters, attenuators or louvres in the line, and kitchen canopy extract where the duct run is long. It still delivers 6667 m³/h at 500 Pa, which is pressure a 4 pole 450mm fan cannot reach.

It is not the fan for noise sensitive spaces or for jobs that need turning down. It is 71 dB(A) at 3m, draws up to 8.8 A, and Elta list no speed controller for it, so treat it as fixed speed. If you need variable speed on a single phase supply, the EC version is the better choice.

Why choose this over alternatives

Against the four pole Elta SLC450/4-1AC, this two pole fan trades noise and running cost for pressure: the 4 pole model moves 6059 m³/h at free air but stops at 100 Pa, while the SLC450/2-1AC still moves around 9904 m³/h at 100 Pa and keeps going to 500 Pa.

If the site has a three phase supply, the Elta SLC450/2A-3AC gives a very similar curve (9929 m³/h free air, 7618 m³/h at 500 Pa) with a peak current of 4.56 A per phase instead of 8.8 A, and it can be inverter controlled. For quiet variable speed on single phase, look at the Elta SLC450-1EC.

Installation notes

  • Mount at any angle, horizontally in a duct run or vertically, but make sure the fan is adequately supported: it weighs 34 kg. AV mounts and mounting feet are available from Elta.
  • The flanges are 530mm outside diameter with 8 holes of 12mm on a 500mm PCD. Use Elta matching flanges and flexible connectors to join it to ductwork.
  • Fit a local isolator, and protect the motor with a starter or controller that has overload protection; fuses and breakers only give short circuit protection. Do not use the isolator for day to day on and off control.
  • Wire to diagram 152-502 for 220-240V single phase. Check rotation and airflow direction at first start and that the running current does not exceed the nameplate.
  • Not suitable for corrosive or explosive atmospheres. Inspect and clean the impeller, motor and guards at least every 12 months.

You'll also need

  • Elta matching flanges 450mm (061B-0450) (sold each, one per ducted side)
  • Elta APK450/003 ancillary pack (flexible connections, matching flanges, AV mounts and mounting feet in one code; available to order, ask us)

Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.

Specifications

Model SLC450/2-1AC
Type Long cased axial fan
Diameter 450mm
Max airflow 10537 m³/h
Static pressure 500 Pa
Motor Single phase AC, 220-240V 50Hz, 2 pole, 2815 rpm
Power 2.05 kW (8.8 A)
Noise 71 dB(A) at 3m
IP rating IP55
Warranty 1 Year Manufacturer
Airflow at 500 Pa 6667 m³/h
Case length (dimension C) 375mm
Flange 530mm OD, 8 holes 12mm on 500mm PCD
Weight 34 kg
Overall efficiency 45.9% (FMEG N 50)
Wiring diagram 152-502
Ambient temperature -20°C to +54°C
Casing Hot dip galvanised steel

Manuals & Guides

Product Description

The Elta SLC450/2-1AC is a 450mm Revolution long cased axial fan and the only two pole single phase model at this size. It moves up to 10537 m³/h at free air and 6667 m³/h against 500 Pa, from a 2 pole single phase AC motor running at 2815 rpm.

The casing is heavy gauge steel, hot dip galvanised to BS EN ISO 1461 and suitable for external mounting, with a die cast aluminium aerofoil impeller. The motor is IP55 with sealed for life bearings, wired to an IP55 terminal box on the outside of the case. No speed controller is listed for this model, so it runs at fixed speed. Elta give a 12 month warranty.

  • 1 Phase
  • AC Motor
  • Up to 10537 m³/h
  • Fixed Speed

What it is best used for

High resistance duties where only a single phase supply is available: long ducted extract runs from workshops, farm buildings and plant rooms, systems with filters, attenuators or louvres in the line, and kitchen canopy extract where the duct run is long. It still delivers 6667 m³/h at 500 Pa, which is pressure a 4 pole 450mm fan cannot reach.

It is not the fan for noise sensitive spaces or for jobs that need turning down. It is 71 dB(A) at 3m, draws up to 8.8 A, and Elta list no speed controller for it, so treat it as fixed speed. If you need variable speed on a single phase supply, the EC version is the better choice.

Why choose this over alternatives

Against the four pole Elta SLC450/4-1AC, this two pole fan trades noise and running cost for pressure: the 4 pole model moves 6059 m³/h at free air but stops at 100 Pa, while the SLC450/2-1AC still moves around 9904 m³/h at 100 Pa and keeps going to 500 Pa.

If the site has a three phase supply, the Elta SLC450/2A-3AC gives a very similar curve (9929 m³/h free air, 7618 m³/h at 500 Pa) with a peak current of 4.56 A per phase instead of 8.8 A, and it can be inverter controlled. For quiet variable speed on single phase, look at the Elta SLC450-1EC.

Installation notes

  • Mount at any angle, horizontally in a duct run or vertically, but make sure the fan is adequately supported: it weighs 34 kg. AV mounts and mounting feet are available from Elta.
  • The flanges are 530mm outside diameter with 8 holes of 12mm on a 500mm PCD. Use Elta matching flanges and flexible connectors to join it to ductwork.
  • Fit a local isolator, and protect the motor with a starter or controller that has overload protection; fuses and breakers only give short circuit protection. Do not use the isolator for day to day on and off control.
  • Wire to diagram 152-502 for 220-240V single phase. Check rotation and airflow direction at first start and that the running current does not exceed the nameplate.
  • Not suitable for corrosive or explosive atmospheres. Inspect and clean the impeller, motor and guards at least every 12 months.

You'll also need

  • Elta matching flanges 450mm (061B-0450) (sold each, one per ducted side)
  • Elta APK450/003 ancillary pack (flexible connections, matching flanges, AV mounts and mounting feet in one code; available to order, ask us)

Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.

Specifications

Model SLC450/2-1AC
Type Long cased axial fan
Diameter 450mm
Max airflow 10537 m³/h
Static pressure 500 Pa
Motor Single phase AC, 220-240V 50Hz, 2 pole, 2815 rpm
Power 2.05 kW (8.8 A)
Noise 71 dB(A) at 3m
IP rating IP55
Warranty 1 Year Manufacturer
Airflow at 500 Pa 6667 m³/h
Case length (dimension C) 375mm
Flange 530mm OD, 8 holes 12mm on 500mm PCD
Weight 34 kg
Overall efficiency 45.9% (FMEG N 50)
Wiring diagram 152-502
Ambient temperature -20°C to +54°C
Casing Hot dip galvanised steel

Manuals & Guides

Delivery & Returns

Our Price Match Promise

Payment Methods

American Express Apple Pay Diners Club Discover Google Pay Maestro Mastercard PayPal Shop Pay Union Pay Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

What size duct does the Elta SLC450/2-1AC fit?

It is a 450mm fan with 450mm inside the casing. The flanges are 530mm outside diameter with 8 holes of 12mm on a 500mm PCD, and the case is 375mm long (dimension C).

How much air does it move?

Up to 10537 m³/h (2.927 m³/s) at free air, falling to 6667 m³/h at 500 Pa, the highest pressure in Elta's table for this model.

Is the SLC450/2-1AC single or three phase?

Single phase, 220-240V 50Hz. Peak current is 8.8 A.

Can I control the speed of the SLC450/2-1AC?

Elta's accessory table lists no speed controller for this two pole single phase model, so treat it as fixed speed. If you need variable speed, the SLC450-1EC or the three phase SLC450/2A-3AC with an Eltadrive inverter are the usual alternatives.

How noisy is it?

71 dB(A) at 3m in free field, per Elta's data. Elta offer podded and unpodded silencers in 1D and 2D lengths for this size if you need it quieter.

Can it be mounted outside or vertically?

Yes. The galvanised casing is suitable for external mounting as standard and the fan can be mounted at any angle. For explosive atmospheres you need the ATEX rated Elta SLCX range instead.