Elta SDA560/46-3AC Raptor Case Mounted Axial Fan Three Phase AC - 560mm
Suggested products
Free 14 day returns
Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.
Why choose eFans?
- Bulk pricing available
- Free help and advice
- Fast quotes, usually within the hour
- Huge range with next-day delivery
- Credit accounts available
Delivery and Warranty
Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days.
£7.95
Next Working Day Delivery
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays)
£15.95
Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95
Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95
Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95
Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95
Product Details
Downloads
Specifications
Product specifications
| Model | SDA560/46-3AC |
| Type | Cased axial fan, short case, two speed |
| Diameter | 560mm |
| Max airflow | 11153 m³/h |
| Static pressure | 200 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 4/6 pole, 1295/916 rpm |
| Power | 1169 W (2.52 A peak) high speed |
| Noise | 57 dB(A) at 3m |
| IP rating | IP54 motor, IP55 terminal box |
| Warranty | 1 Year Manufacturer |
Summary
See more specification See less specification
The Elta SDA560/46-3AC is a 560mm Raptor SDA short cased axial fan for fitting in 560mm ductwork. It moves up to 11153 m³/h in free air, 9688 m³/h at 100 Pa and still 7906 m³/h at 200 Pa, the highest pressure in Elta's published table for this model. On low speed (star) it moves 8453 m³/h for quieter running.
The 4/6 pole three phase AC external rotor motor (380-415V 50Hz) runs at 1295 rpm in delta and 916 rpm in star, drawing 1169 W and 2.52 A on high speed. It is insulated to Class F with integral thermal overload protection. The Ziehl-Abegg FE2owlet aerofoil impeller has serrated trailing edges and winglets for lower noise, the mild steel case is powder coated in RAL 7045 with an IP55 terminal box, the motor is IP54, and Elta give a 12 month warranty.
- 3 Phase
- AC Motor
- Up to 11153 m³/h
- Speed Controllable
What it is best used for
High volume ducted extract or supply on 560mm duct for sports halls, factories, industrial units, warehousing and retail parks. At 50 Pa it moves 10526 m³/h, roughly 6 air changes an hour in a space of about 1750 m³.
It still gives 7906 m³/h at 200 Pa, but Elta publish no figures for it beyond that, so very high resistance systems need a mixed flow or centrifugal fan. It is not suitable for corrosive or explosive atmospheres, and the air must stay between -20°C and +70°C. It needs a 380 to 415V three phase supply.
Why choose this over alternatives
There are 3 Raptor SDA models in the 560mm case, and the choice comes down to supply, noise and control. This three phase version has two built in speeds from star/delta switching and draws only 2.52 A per phase on high speed. In the same size there is also the Elta SDA560/4-1AC (4 pole single phase, 11678 m³/h, 63 dB(A)) and the Elta SDA560/6-1AC (6 pole single phase, 7891 m³/h, 52 dB(A)).
For a smaller duct the Elta SDA500/46-3AC gives 8813 m³/h. If the fan will sit in a wall or panel rather than in a duct, the Elta SPA560/46-3AC plate fan uses the same Raptor impeller and motor family on a square mounting plate.
Installation notes
- Fit it in the duct run at any angle, securely supported, with access for maintenance. The case is 272mm long with 16 holes of 12mm on a 605mm PCD at each end for Elta matching flanges 061A-0560-C, and mounting feet 060A-0560-C are available.
- Wire to Elta diagram 152-108: delta connection gives high speed, star gives low speed, and a star/delta switch can select between them. Swap any two supply phases to reverse rotation.
- For variable speed Elta pair it with the 149-TC33 three phase transformer controller. Wire the thermal contacts (TB TB) into the starter or controller circuit so the motor is protected.
- Fit a local means of isolation, and site the discharge so exhaust cannot be drawn back into a room through the open flue of a gas or fuel burning appliance.
- At first start check rotation, airflow direction and that the running current is within the rating plate. Inspect and clean the blades and guards at least every 12 months.
You'll also need
- Elta 149-TC33 three phase five step transformer controller available to order, ask us
- Elta ancillary pack APK560SCD/002 (flexible connections, matching flanges, anti-vibration mounts and mounting feet) available to order, ask us
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SDA560/46-3AC |
| Type | Cased axial fan, short case, two speed |
| Diameter | 560mm |
| Max airflow | 11153 m³/h |
| Static pressure | 200 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 4/6 pole, 1295/916 rpm |
| Power | 1169 W (2.52 A peak) high speed |
| Noise | 57 dB(A) at 3m |
| IP rating | IP54 motor, IP55 terminal box |
| Warranty | 1 Year Manufacturer |
| Airflow at 50 Pa | 10526 m³/h |
| Airflow at 100 Pa | 9688 m³/h |
| Airflow at 150 Pa | 8831 m³/h |
| Low speed airflow (star) | 8453 m³/h |
| Low speed power | 654 W (1.27 A) |
| Low speed noise | 51 dB(A) at 3m |
| Overall efficiency | 33.7% at best efficiency point |
| FMEG | 40 |
| Case | 272mm long, 560mm internal diameter, 641mm flange diameter |
| Flange fixings | 16 holes 12mm on 605mm PCD |
| Impeller | Ziehl-Abegg FE2owlet aerofoil with serrated trailing edges |
| Finish | Powder coated mild steel, RAL 7045 |
| Operating temperature | -20°C to +70°C, up to 95% RH |
| Weight | 25.5 kg |
| Wiring diagram | 152-108 |
Manuals & Guides
Product Description
The Elta SDA560/46-3AC is a 560mm Raptor SDA short cased axial fan for fitting in 560mm ductwork. It moves up to 11153 m³/h in free air, 9688 m³/h at 100 Pa and still 7906 m³/h at 200 Pa, the highest pressure in Elta's published table for this model. On low speed (star) it moves 8453 m³/h for quieter running.
The 4/6 pole three phase AC external rotor motor (380-415V 50Hz) runs at 1295 rpm in delta and 916 rpm in star, drawing 1169 W and 2.52 A on high speed. It is insulated to Class F with integral thermal overload protection. The Ziehl-Abegg FE2owlet aerofoil impeller has serrated trailing edges and winglets for lower noise, the mild steel case is powder coated in RAL 7045 with an IP55 terminal box, the motor is IP54, and Elta give a 12 month warranty.
- 3 Phase
- AC Motor
- Up to 11153 m³/h
- Speed Controllable
What it is best used for
High volume ducted extract or supply on 560mm duct for sports halls, factories, industrial units, warehousing and retail parks. At 50 Pa it moves 10526 m³/h, roughly 6 air changes an hour in a space of about 1750 m³.
It still gives 7906 m³/h at 200 Pa, but Elta publish no figures for it beyond that, so very high resistance systems need a mixed flow or centrifugal fan. It is not suitable for corrosive or explosive atmospheres, and the air must stay between -20°C and +70°C. It needs a 380 to 415V three phase supply.
Why choose this over alternatives
There are 3 Raptor SDA models in the 560mm case, and the choice comes down to supply, noise and control. This three phase version has two built in speeds from star/delta switching and draws only 2.52 A per phase on high speed. In the same size there is also the Elta SDA560/4-1AC (4 pole single phase, 11678 m³/h, 63 dB(A)) and the Elta SDA560/6-1AC (6 pole single phase, 7891 m³/h, 52 dB(A)).
For a smaller duct the Elta SDA500/46-3AC gives 8813 m³/h. If the fan will sit in a wall or panel rather than in a duct, the Elta SPA560/46-3AC plate fan uses the same Raptor impeller and motor family on a square mounting plate.
Installation notes
- Fit it in the duct run at any angle, securely supported, with access for maintenance. The case is 272mm long with 16 holes of 12mm on a 605mm PCD at each end for Elta matching flanges 061A-0560-C, and mounting feet 060A-0560-C are available.
- Wire to Elta diagram 152-108: delta connection gives high speed, star gives low speed, and a star/delta switch can select between them. Swap any two supply phases to reverse rotation.
- For variable speed Elta pair it with the 149-TC33 three phase transformer controller. Wire the thermal contacts (TB TB) into the starter or controller circuit so the motor is protected.
- Fit a local means of isolation, and site the discharge so exhaust cannot be drawn back into a room through the open flue of a gas or fuel burning appliance.
- At first start check rotation, airflow direction and that the running current is within the rating plate. Inspect and clean the blades and guards at least every 12 months.
You'll also need
- Elta 149-TC33 three phase five step transformer controller available to order, ask us
- Elta ancillary pack APK560SCD/002 (flexible connections, matching flanges, anti-vibration mounts and mounting feet) available to order, ask us
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SDA560/46-3AC |
| Type | Cased axial fan, short case, two speed |
| Diameter | 560mm |
| Max airflow | 11153 m³/h |
| Static pressure | 200 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 4/6 pole, 1295/916 rpm |
| Power | 1169 W (2.52 A peak) high speed |
| Noise | 57 dB(A) at 3m |
| IP rating | IP54 motor, IP55 terminal box |
| Warranty | 1 Year Manufacturer |
| Airflow at 50 Pa | 10526 m³/h |
| Airflow at 100 Pa | 9688 m³/h |
| Airflow at 150 Pa | 8831 m³/h |
| Low speed airflow (star) | 8453 m³/h |
| Low speed power | 654 W (1.27 A) |
| Low speed noise | 51 dB(A) at 3m |
| Overall efficiency | 33.7% at best efficiency point |
| FMEG | 40 |
| Case | 272mm long, 560mm internal diameter, 641mm flange diameter |
| Flange fixings | 16 holes 12mm on 605mm PCD |
| Impeller | Ziehl-Abegg FE2owlet aerofoil with serrated trailing edges |
| Finish | Powder coated mild steel, RAL 7045 |
| Operating temperature | -20°C to +70°C, up to 95% RH |
| Weight | 25.5 kg |
| Wiring diagram | 152-108 |
Manuals & Guides
Delivery & Returns
Our Price Match Promise
Payment Methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
How much air does the Elta SDA560/46-3AC move?
Up to 11153 m³/h in free air, 10526 m³/h at 50 Pa, 9688 m³/h at 100 Pa and 7906 m³/h at 200 Pa. On low speed it moves 8453 m³/h in free air.
What size duct does the SDA560/46-3AC fit?
560mm. The case has a 560mm internal diameter and 16 flange holes of 12mm on a 605mm PCD at each end, which match Elta's 061A-0560-C matching flanges.
Is it two speed?
Yes. Delta connection runs it at 1295 rpm and star at 916 rpm. For five step variable speed Elta specify the 149-TC33 three phase transformer controller, which we can order in.
How noisy is it?
Elta quote 57 dB(A) at the inlet and 57 dB(A) at the outlet at 3m on high speed, and 51 dB(A) on low speed. Matching 1D and 2D flanged silencers (068-0560) are available to order if you need it quieter.
What power supply does it need?
A three phase 380-415V 50Hz supply. Peak current is 2.52 A at 400V, and Elta wiring diagram 152-108 applies. It must be wired by a qualified electrician with a local isolator.
Can it be mounted vertically or outside the building?
It can be mounted at any angle, horizontal or vertical. The motor is IP54 with an IP55 terminal box and the fan handles air from -20°C to +70°C, but it is designed to sit in ductwork rather than be exposed to the weather; on an external wall fit a weather cowl such as Elta SWC56/63.