Elta SCP560/4-1AC Compact Plate Axial Fan Single Phase AC - 560mm
Suggested products
Free 14 day returns
Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.
Why choose eFans?
- Bulk pricing available
- Free help and advice
- Fast quotes, usually within the hour
- Huge range with next-day delivery
- Credit accounts available
Delivery and Warranty
Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days.
£7.95
Next Working Day Delivery
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays)
£15.95
Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95
Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95
Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95
Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95
Product Details
Downloads
Specifications
Product specifications
| Model | SCP560/4-1AC |
| Type | Plate mounted axial fan |
| Diameter | 560mm |
| Max airflow | 12056 m³/h |
| Static pressure | 150 Pa |
| Motor | Single phase AC, 220-240V 50Hz, 4 pole, 1315 rpm |
| Power | 920 W (4.90 A) |
| Noise | 58 dB(A) at 3m |
| IP rating | IP55 terminal box |
| Warranty | 1 Year Manufacturer |
Summary
See more specification See less specification
The Elta SCP560/4-1AC is a 560mm Compact SCP plate mounted axial fan with a single phase 4 pole AC motor, moving up to 12056 m³/h in free air and working against static pressures up to 150 Pa. It is built for moving large volumes of air against low resistance, straight through a wall, panel or bulkhead.
The 220-240V induction motor runs at 1315 rpm with greased for life ball bearings, drawing 920 W and 4.90 A. The Series 1 impeller has adjustable pitch GRP aerofoil blades, the mild steel plate and motor are powder coated and the guards epoxy coated, an IP55 terminal box is fitted on 550mm of flexible conduit, and Elta give a 12 month warranty.
- 1 Phase
- AC Motor
- Up to 12056 m³/h
- Speed Controllable
What it is best used for
Through-wall extract or supply on a single phase supply in warehouses, distribution sheds, factories, sports halls and large industrial units, often as a bank of fans along one wall. At 12056 m³/h it gives about 6 air changes an hour in a space of roughly 1984 m³, for example 31m x 16m with a 4m ceiling.
It is a low pressure fan. The datasheet shows airflow only up to 150 Pa, so it is the wrong choice for ducted systems or heavy louvres; use a cased axial or inline mixed flow fan there. When speed controlled Elta limit the air temperature to +50°C (+70°C at fixed speed), and it is not suitable for corrosive or explosive atmospheres.
Why choose this over alternatives
If you have a three phase supply, the Elta SCP560/4-3AC is the same size (11959 m³/h, up to 100 Pa, 951 W, 60 dB(A)). The single phase Elta SCP560-1EC uses an EC motor with built in speed control and gives 10739 m³/h, up to 250 Pa, 932 W, 67 dB(A), so it suits sites that need more pressure or BMS control. Elta's Raptor Elta SPA560/4-1AC is the alternative 560mm single phase plate fan with a Ziehl-Abegg impeller (12578 m³/h, up to 200 Pa, 1.15 kW, 63 dB(A)).
Installation notes
- Mount the 725 x 725mm fan plate securely at any angle using the four 10mm holes on 670mm centres. Make sure the structure can carry its 24 kg and leave access for maintenance.
- The motor is prewired to an IP55 terminal box on 550mm of 20mm flexible conduit. Wire to Elta diagram 152-500 and make all earth connections; the thermal cut-out must be wired into the starter or controller control circuit.
- For speed control Elta list the 149-TC18 five step transformer controller (8 A). Diagram 152-500 also shows connection to the 149-EL31TK and 149-EL61TK electronic controllers; choose one rated above the motor current.
- Fit a local means of isolation, but do not use the isolator for day to day on and off control. Elta warn this shortens motor life; use a controller or switch instead.
- At first start check rotation, airflow direction and that the running current does not exceed the rating plate. Inspect and clean blades and guards at least every 12 months.
You'll also need
- Elta 149-TC18 five step transformer controller (8 amp) for speed control.
- Elta 064-0560-C louvre shutter available to order, ask us
- Elta 078-0560-C impeller side guard available to order, ask us
- Elta SWC56/63 wall cowl available to order, ask us
Browse more plate axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SCP560/4-1AC |
| Type | Plate mounted axial fan |
| Diameter | 560mm |
| Max airflow | 12056 m³/h |
| Static pressure | 150 Pa |
| Motor | Single phase AC, 220-240V 50Hz, 4 pole, 1315 rpm |
| Power | 920 W (4.90 A) |
| Noise | 58 dB(A) at 3m |
| IP rating | IP55 terminal box |
| Warranty | 1 Year Manufacturer |
| Airflow at 50 Pa | 10904 m³/h |
| Airflow at 100 Pa | 9450 m³/h |
| Airflow at 150 Pa | 7488 m³/h |
| Overall efficiency | 34.4% |
| FMEG | 41 |
| Plate size | 725 x 725mm |
| Fixing centres | 670mm, 4 holes 10mm |
| Weight | 24 kg |
| Operating temperature | -20°C to +70°C fixed speed, -20°C to +50°C speed controlled |
| Wiring diagram | 152-500 |
Manuals & Guides
Product Description
The Elta SCP560/4-1AC is a 560mm Compact SCP plate mounted axial fan with a single phase 4 pole AC motor, moving up to 12056 m³/h in free air and working against static pressures up to 150 Pa. It is built for moving large volumes of air against low resistance, straight through a wall, panel or bulkhead.
The 220-240V induction motor runs at 1315 rpm with greased for life ball bearings, drawing 920 W and 4.90 A. The Series 1 impeller has adjustable pitch GRP aerofoil blades, the mild steel plate and motor are powder coated and the guards epoxy coated, an IP55 terminal box is fitted on 550mm of flexible conduit, and Elta give a 12 month warranty.
- 1 Phase
- AC Motor
- Up to 12056 m³/h
- Speed Controllable
What it is best used for
Through-wall extract or supply on a single phase supply in warehouses, distribution sheds, factories, sports halls and large industrial units, often as a bank of fans along one wall. At 12056 m³/h it gives about 6 air changes an hour in a space of roughly 1984 m³, for example 31m x 16m with a 4m ceiling.
It is a low pressure fan. The datasheet shows airflow only up to 150 Pa, so it is the wrong choice for ducted systems or heavy louvres; use a cased axial or inline mixed flow fan there. When speed controlled Elta limit the air temperature to +50°C (+70°C at fixed speed), and it is not suitable for corrosive or explosive atmospheres.
Why choose this over alternatives
If you have a three phase supply, the Elta SCP560/4-3AC is the same size (11959 m³/h, up to 100 Pa, 951 W, 60 dB(A)). The single phase Elta SCP560-1EC uses an EC motor with built in speed control and gives 10739 m³/h, up to 250 Pa, 932 W, 67 dB(A), so it suits sites that need more pressure or BMS control. Elta's Raptor Elta SPA560/4-1AC is the alternative 560mm single phase plate fan with a Ziehl-Abegg impeller (12578 m³/h, up to 200 Pa, 1.15 kW, 63 dB(A)).
Installation notes
- Mount the 725 x 725mm fan plate securely at any angle using the four 10mm holes on 670mm centres. Make sure the structure can carry its 24 kg and leave access for maintenance.
- The motor is prewired to an IP55 terminal box on 550mm of 20mm flexible conduit. Wire to Elta diagram 152-500 and make all earth connections; the thermal cut-out must be wired into the starter or controller control circuit.
- For speed control Elta list the 149-TC18 five step transformer controller (8 A). Diagram 152-500 also shows connection to the 149-EL31TK and 149-EL61TK electronic controllers; choose one rated above the motor current.
- Fit a local means of isolation, but do not use the isolator for day to day on and off control. Elta warn this shortens motor life; use a controller or switch instead.
- At first start check rotation, airflow direction and that the running current does not exceed the rating plate. Inspect and clean blades and guards at least every 12 months.
You'll also need
- Elta 149-TC18 five step transformer controller (8 amp) for speed control.
- Elta 064-0560-C louvre shutter available to order, ask us
- Elta 078-0560-C impeller side guard available to order, ask us
- Elta SWC56/63 wall cowl available to order, ask us
Browse more plate axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SCP560/4-1AC |
| Type | Plate mounted axial fan |
| Diameter | 560mm |
| Max airflow | 12056 m³/h |
| Static pressure | 150 Pa |
| Motor | Single phase AC, 220-240V 50Hz, 4 pole, 1315 rpm |
| Power | 920 W (4.90 A) |
| Noise | 58 dB(A) at 3m |
| IP rating | IP55 terminal box |
| Warranty | 1 Year Manufacturer |
| Airflow at 50 Pa | 10904 m³/h |
| Airflow at 100 Pa | 9450 m³/h |
| Airflow at 150 Pa | 7488 m³/h |
| Overall efficiency | 34.4% |
| FMEG | 41 |
| Plate size | 725 x 725mm |
| Fixing centres | 670mm, 4 holes 10mm |
| Weight | 24 kg |
| Operating temperature | -20°C to +70°C fixed speed, -20°C to +50°C speed controlled |
| Wiring diagram | 152-500 |
Manuals & Guides
Delivery & Returns
Our Price Match Promise
Payment Methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
How much air does the Elta SCP560/4-1AC move?
Up to 12056 m³/h in free air, and 10904 m³/h at 50 Pa, 9450 m³/h at 100 Pa and 7488 m³/h at 150 Pa.
What size hole and plate does it need?
It fits a 560mm opening. The square plate is 725 x 725mm with four 10mm fixing holes on 670mm centres.
Can it run on a normal 230V supply?
Yes. It is a single phase 220-240V 50Hz fan drawing 920 W and 4.90 A.
Which speed controller suits it?
Elta list the 149-TC18 transformer controller, which we stock. When speed controlled the maximum air temperature drops to +50°C.
How noisy is it?
Elta quote 58 dB(A) at 3m at full speed.
Can it be mounted horizontally?
Yes. Elta say the fan can be mounted at any angle, so it suits walls, bulkheads and horizontal panels.