Elta SCD630 Cased Axial Fan Three Phase AC - 630mm
Suggested products
Free 14 day returns
Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.
Why choose eFans?
- Bulk pricing available
- Free help and advice
- Fast quotes, usually within the hour
- Huge range with next-day delivery
- Credit accounts available
Delivery and Warranty
Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days.
£7.95
Next Working Day Delivery
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays)
£15.95
Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95
Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95
Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95
Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95
Product Details
Downloads
Specifications
Product specifications
| Model | SCD630/4-3AC |
| Type | Compact cased axial fan |
| Diameter | 630mm |
| Max airflow | 15296 m³/h |
| Static pressure | 150 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 4 pole, 1435 rpm |
| Power | 1.222 kW (2.70 A) |
| Noise | 65 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
Summary
See more specification See less specification
The Elta SCD630/4-3AC is a 630mm Compact SCD cased axial fan with a short 250mm case, built for moving large volumes of air against low resistance. It moves up to 15296 m³/h at free air and 11070 m³/h against 150 Pa, from a 4 pole three phase AC motor running at 1435 rpm.
The mild steel casing is powder coated in Telegrey 1 (RAL 7045) with the motor and adjustable pitch aerofoil impeller held within its length, and an IP55 terminal box is fitted as standard. The three phase TENV motor is IP55, multi voltage (star 400V as supplied, or delta 230V three phase) and suits the Eltadrive inverter range or a 149-TC310 transformer controller. It is rated for air from -20°C to +70°C at fixed speed (+50°C with a speed controller) and Elta give a 12 month warranty.
- 3 Phase
- AC Motor
- Up to 15296 m³/h
- Speed Controllable
What it is best used for
Moving a lot of air against low resistance on a three phase supply: warehousing, factories, large sports halls and industrial units, mounted in a duct run or on a wall. It moves 15296 m³/h at free air on 1.222 kW, at 65 dB(A) at 3m.
It reaches 150 Pa, but airflow falls to 11070 m³/h there, so it suits short to medium duct runs rather than long filtered systems.
Why choose this over alternatives
The single phase Elta SCD630/4-1AC moves 17413 m³/h at the same size. Choose this three phase model where you have a three phase supply and want inverter control, as Elta rate the three phase motor for use with the Eltadrive range.
Against the long cased Elta SLC630/4A-3AC (13403 m³/h, to 250 Pa), the SCD is a much shorter and lighter fan (250mm case, 30 kg) with a powder coated finish, and costs less. Choose the SLC for higher pressure, external mounting (it is hot dip galvanised and rated for outdoor use as standard) or heavier industrial duty.
Installation notes
- The fan is short (250mm) and light (30 kg), so it fits in a duct run or on a wall where space is tight. Mounting feet and AV mounts are available from Elta.
- The flanges are 709mm outside diameter with 16 holes of 12mm on a 674mm PCD. Use Elta matching flanges and flexible connectors to join it to ductwork.
- Supplied star (Y) connected for 400V three phase, wiring diagram 152-611, via the fitted IP55 terminal box (21mm cable entry). The motor can be reconnected to delta for 230V three phase from an inverter.
- If you run it on a speed controller, keep the air temperature at or below +50°C (Elta's limit with a controller); at fixed speed it is rated to +70°C.
You'll also need
- Elta matching flanges 061A-0630-C (sold each, one per ducted side; available to order, ask us)
- Elta 149-TC310 three phase transformer speed controller (available to order, ask us)
- Eltadrive 149-ODE3-14150-3KA1B inverter for a three phase supply (or 149-ODE3-12150-1K1B from single phase; available to order, ask us)
- Elta APK630SCD/002 ancillary pack (flexible connections, matching flanges, AV mounts and mounting feet in one code; available to order, ask us)
- Elta SWC56/63 wall cowl (for wall mounted installs; available to order, ask us)
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SCD630/4-3AC |
| Type | Compact cased axial fan |
| Diameter | 630mm |
| Max airflow | 15296 m³/h |
| Static pressure | 150 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 4 pole, 1435 rpm |
| Power | 1.222 kW (2.70 A) |
| Noise | 65 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
| Airflow at 150 Pa | 11070 m³/h |
| Case length (dimension C) | 250mm |
| Flange | 709mm OD, 16 holes 12mm on 674mm PCD |
| Weight | 30 kg |
| Overall efficiency | 37.5% (FMEG N 43) |
| Motor connection | Star (Y) |
| Wiring diagram | 152-611 |
| Air temperature | -20°C to +70°C fixed speed, +50°C speed controlled |
| Casing | Powder coated mild steel, RAL 7045 |
Manuals & Guides
Product Description
The Elta SCD630/4-3AC is a 630mm Compact SCD cased axial fan with a short 250mm case, built for moving large volumes of air against low resistance. It moves up to 15296 m³/h at free air and 11070 m³/h against 150 Pa, from a 4 pole three phase AC motor running at 1435 rpm.
The mild steel casing is powder coated in Telegrey 1 (RAL 7045) with the motor and adjustable pitch aerofoil impeller held within its length, and an IP55 terminal box is fitted as standard. The three phase TENV motor is IP55, multi voltage (star 400V as supplied, or delta 230V three phase) and suits the Eltadrive inverter range or a 149-TC310 transformer controller. It is rated for air from -20°C to +70°C at fixed speed (+50°C with a speed controller) and Elta give a 12 month warranty.
- 3 Phase
- AC Motor
- Up to 15296 m³/h
- Speed Controllable
What it is best used for
Moving a lot of air against low resistance on a three phase supply: warehousing, factories, large sports halls and industrial units, mounted in a duct run or on a wall. It moves 15296 m³/h at free air on 1.222 kW, at 65 dB(A) at 3m.
It reaches 150 Pa, but airflow falls to 11070 m³/h there, so it suits short to medium duct runs rather than long filtered systems.
Why choose this over alternatives
The single phase Elta SCD630/4-1AC moves 17413 m³/h at the same size. Choose this three phase model where you have a three phase supply and want inverter control, as Elta rate the three phase motor for use with the Eltadrive range.
Against the long cased Elta SLC630/4A-3AC (13403 m³/h, to 250 Pa), the SCD is a much shorter and lighter fan (250mm case, 30 kg) with a powder coated finish, and costs less. Choose the SLC for higher pressure, external mounting (it is hot dip galvanised and rated for outdoor use as standard) or heavier industrial duty.
Installation notes
- The fan is short (250mm) and light (30 kg), so it fits in a duct run or on a wall where space is tight. Mounting feet and AV mounts are available from Elta.
- The flanges are 709mm outside diameter with 16 holes of 12mm on a 674mm PCD. Use Elta matching flanges and flexible connectors to join it to ductwork.
- Supplied star (Y) connected for 400V three phase, wiring diagram 152-611, via the fitted IP55 terminal box (21mm cable entry). The motor can be reconnected to delta for 230V three phase from an inverter.
- If you run it on a speed controller, keep the air temperature at or below +50°C (Elta's limit with a controller); at fixed speed it is rated to +70°C.
You'll also need
- Elta matching flanges 061A-0630-C (sold each, one per ducted side; available to order, ask us)
- Elta 149-TC310 three phase transformer speed controller (available to order, ask us)
- Eltadrive 149-ODE3-14150-3KA1B inverter for a three phase supply (or 149-ODE3-12150-1K1B from single phase; available to order, ask us)
- Elta APK630SCD/002 ancillary pack (flexible connections, matching flanges, AV mounts and mounting feet in one code; available to order, ask us)
- Elta SWC56/63 wall cowl (for wall mounted installs; available to order, ask us)
Browse more cased axial fans, axial fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SCD630/4-3AC |
| Type | Compact cased axial fan |
| Diameter | 630mm |
| Max airflow | 15296 m³/h |
| Static pressure | 150 Pa |
| Motor | Three phase AC, 380-415V 50Hz, 4 pole, 1435 rpm |
| Power | 1.222 kW (2.70 A) |
| Noise | 65 dB(A) at 3m |
| IP rating | IP55 |
| Warranty | 1 Year Manufacturer |
| Airflow at 150 Pa | 11070 m³/h |
| Case length (dimension C) | 250mm |
| Flange | 709mm OD, 16 holes 12mm on 674mm PCD |
| Weight | 30 kg |
| Overall efficiency | 37.5% (FMEG N 43) |
| Motor connection | Star (Y) |
| Wiring diagram | 152-611 |
| Air temperature | -20°C to +70°C fixed speed, +50°C speed controlled |
| Casing | Powder coated mild steel, RAL 7045 |
Manuals & Guides
Delivery & Returns
Our Price Match Promise
Payment Methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
What size duct does the Elta SCD630/4-3AC fit?
It is a 630mm fan with 630mm inside the casing. The flanges are 709mm outside diameter with 16 holes of 12mm on a 674mm PCD, and the case is 250mm long.
How much air does it move?
Up to 15296 m³/h (4.249 m³/s) at free air, falling to 11070 m³/h at 150 Pa, the highest pressure in Elta's table for this model.
Is the SCD630/4-3AC single or three phase?
Three phase, 380-415V 50Hz, star connected as supplied. Peak current is 2.70 A.
Can I control the speed of the SCD630/4-3AC?
Yes. Elta list the 149-TC310 three phase transformer controller, or an Eltadrive inverter: 149-ODE3-14150-3KA1B on a three phase supply or 149-ODE3-12150-1K1B from single phase. With a speed controller Elta rate the fan for air up to +50°C, against +70°C at fixed speed.
How noisy is it?
65 dB(A) at 3m in free field, per Elta's data. Elta offer 1D and 2D silencers (068-0630 codes) for this size if you need it quieter.
Can it be mounted on a wall?
Yes. It can go in a duct run or on a wall, and Elta list the SWC56/63 wall cowl and an impeller side guard (078C-0630-C) for wall installs. For exposed outdoor positions, the hot dip galvanised SLC range is rated for external mounting as standard.