Elta Multiflow SEL355/4-1AC Mixed Flow Inline Fan Single Phase AC - 355mm
Suggested products
Free 14 day returns
Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.
Why choose eFans?
- Bulk pricing available
- Free help and advice
- Fast quotes, usually within the hour
- Huge range with next-day delivery
- Credit accounts available
Delivery and Warranty
Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days.
£7.95
Next Working Day Delivery
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays)
£15.95
Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95
Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95
Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95
Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95
Product Details
Downloads
Specifications
Product specifications
| Model | SEL355/4-1AC |
| Type | Mixed flow inline duct fan |
| Duct size | 355mm |
| Max airflow | 2570 m³/h |
| Static pressure | 250 Pa |
| Motor | Single phase AC, 220 to 240V 50Hz, 4 pole, 1438 rpm |
| Power | 0.15 kW (0.7 A) |
| Noise | 43 dB(A) inlet, 45 dB(A) outlet at 3m |
| IP rating | IPX4 casing, IP44 terminal box |
| Warranty | 1 Year Manufacturer |
Summary
See more specification See less specification
The Elta Multiflow SEL355/4-1AC is a 355mm mixed flow inline duct fan with a single phase 4 pole AC motor, moving up to 2570 m³/h in free air and 2124 m³/h against 100 Pa. A diagonal mixed flow impeller and 3D stator guide vanes give it far more pressure than an axial fan of the same diameter.
The motor runs at 1438 rpm on 220 to 240V 50Hz, absorbing 0.15 kW at its best efficiency point with integral thermal overload protection, and it is wired through an integral IP44 terminal box. The casing is weatherproofed to IPX4, the fan mounts at any angle on its integral bracket, and Elta give a 12 month warranty.
- 1 Phase
- AC Motor
- Up to 2570 m³/h
- Speed Controllable
What it is best used for
Quiet, low pressure ventilation on 355mm duct from a single phase supply: offices, classrooms, meeting rooms and hotel areas where the duct run is short and the fan sits near people. It moves 2124 m³/h at 100 Pa at just 43 dB(A) inlet at 3m.
It is a low pressure 4 pole fan: the curve drops to 353 m³/h at 200 Pa and 108 m³/h at 250 Pa. Do not use it on systems above about 150 Pa; the 2 pole SEL355/2-1AC is the high pressure version of this size.
Why choose this over alternatives
Against the 2 pole SEL355/2-1AC, this 4 pole model uses a fraction of the power (0.15 kW against 0.955 kW) and is much quieter (43 against 59 dB(A) inlet at 3m), at the cost of pressure. On a short, low resistance run it is the cheaper fan to run and the easier one to live with.
Installation notes
- The fan can be mounted in any orientation. Slide it into the duct and fix it with the integral mounting bracket, making sure the ductwork is not strained, and connect duct to both inlet and outlet so no moving parts are accessible.
- Elta recommend padded connection sleeves or fast clamps (018-355-CLAMP) to cut noise transmitted into the ductwork. Run the airflow in the direction marked on the casing.
- Wire into the integral IP44 terminal box to Elta diagram 152-540. Elta specify the 149-TC12 5 step transformer controller (2 A) for speed control; at lower steps the fan runs at 1365, 1275 and 940 rpm.
- The internal thermal protection does not protect the motor if the impeller is blocked, so where that could happen fit a motor protection switch with thermal and magnetic release. Fit a means of isolation and earth the fan.
- Install indoors in a dry, condensation free space: Elta's installation manual says SEL fans must not be operated out of doors, and they are not for explosive atmospheres. Clean the impeller and casing at the recommended intervals; an upstream filter extends them.
You'll also need
- Elta 149-TC12 single phase 5 step transformer controller (2 A), available to order, ask us.
- Elta fast clamps 018-355-CLAMP (each) and backdraught damper 018-355-DAMPER, available to order, ask us.
- Elta spigot silencers 068-0355-JF1 (300mm) to 068-0355-JF4 (1200mm), available to order, ask us.
Browse more inline mixed flow fans, inline duct fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SEL355/4-1AC |
| Type | Mixed flow inline duct fan |
| Duct size | 355mm |
| Max airflow | 2570 m³/h |
| Static pressure | 250 Pa |
| Motor | Single phase AC, 220 to 240V 50Hz, 4 pole, 1438 rpm |
| Power | 0.15 kW (0.7 A) |
| Noise | 43 dB(A) inlet, 45 dB(A) outlet at 3m |
| IP rating | IPX4 casing, IP44 terminal box |
| Warranty | 1 Year Manufacturer |
| Airflow at 100 Pa | 2124 m³/h |
| Airflow at 200 Pa | 353 m³/h |
| Overall efficiency | 46.8% at best efficiency point |
| FMEG efficiency grade | N 66 |
| Max ambient temperature | 80°C (nameplate) |
| Breakout noise | 26 dB(A) at 3m |
| Weight | 14 kg |
| Speed controller | 149-TC12 (5 step transformer) |
| Wiring diagram | 152-540 |
Manuals & Guides
Product Description
The Elta Multiflow SEL355/4-1AC is a 355mm mixed flow inline duct fan with a single phase 4 pole AC motor, moving up to 2570 m³/h in free air and 2124 m³/h against 100 Pa. A diagonal mixed flow impeller and 3D stator guide vanes give it far more pressure than an axial fan of the same diameter.
The motor runs at 1438 rpm on 220 to 240V 50Hz, absorbing 0.15 kW at its best efficiency point with integral thermal overload protection, and it is wired through an integral IP44 terminal box. The casing is weatherproofed to IPX4, the fan mounts at any angle on its integral bracket, and Elta give a 12 month warranty.
- 1 Phase
- AC Motor
- Up to 2570 m³/h
- Speed Controllable
What it is best used for
Quiet, low pressure ventilation on 355mm duct from a single phase supply: offices, classrooms, meeting rooms and hotel areas where the duct run is short and the fan sits near people. It moves 2124 m³/h at 100 Pa at just 43 dB(A) inlet at 3m.
It is a low pressure 4 pole fan: the curve drops to 353 m³/h at 200 Pa and 108 m³/h at 250 Pa. Do not use it on systems above about 150 Pa; the 2 pole SEL355/2-1AC is the high pressure version of this size.
Why choose this over alternatives
Against the 2 pole SEL355/2-1AC, this 4 pole model uses a fraction of the power (0.15 kW against 0.955 kW) and is much quieter (43 against 59 dB(A) inlet at 3m), at the cost of pressure. On a short, low resistance run it is the cheaper fan to run and the easier one to live with.
Installation notes
- The fan can be mounted in any orientation. Slide it into the duct and fix it with the integral mounting bracket, making sure the ductwork is not strained, and connect duct to both inlet and outlet so no moving parts are accessible.
- Elta recommend padded connection sleeves or fast clamps (018-355-CLAMP) to cut noise transmitted into the ductwork. Run the airflow in the direction marked on the casing.
- Wire into the integral IP44 terminal box to Elta diagram 152-540. Elta specify the 149-TC12 5 step transformer controller (2 A) for speed control; at lower steps the fan runs at 1365, 1275 and 940 rpm.
- The internal thermal protection does not protect the motor if the impeller is blocked, so where that could happen fit a motor protection switch with thermal and magnetic release. Fit a means of isolation and earth the fan.
- Install indoors in a dry, condensation free space: Elta's installation manual says SEL fans must not be operated out of doors, and they are not for explosive atmospheres. Clean the impeller and casing at the recommended intervals; an upstream filter extends them.
You'll also need
- Elta 149-TC12 single phase 5 step transformer controller (2 A), available to order, ask us.
- Elta fast clamps 018-355-CLAMP (each) and backdraught damper 018-355-DAMPER, available to order, ask us.
- Elta spigot silencers 068-0355-JF1 (300mm) to 068-0355-JF4 (1200mm), available to order, ask us.
Browse more inline mixed flow fans, inline duct fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SEL355/4-1AC |
| Type | Mixed flow inline duct fan |
| Duct size | 355mm |
| Max airflow | 2570 m³/h |
| Static pressure | 250 Pa |
| Motor | Single phase AC, 220 to 240V 50Hz, 4 pole, 1438 rpm |
| Power | 0.15 kW (0.7 A) |
| Noise | 43 dB(A) inlet, 45 dB(A) outlet at 3m |
| IP rating | IPX4 casing, IP44 terminal box |
| Warranty | 1 Year Manufacturer |
| Airflow at 100 Pa | 2124 m³/h |
| Airflow at 200 Pa | 353 m³/h |
| Overall efficiency | 46.8% at best efficiency point |
| FMEG efficiency grade | N 66 |
| Max ambient temperature | 80°C (nameplate) |
| Breakout noise | 26 dB(A) at 3m |
| Weight | 14 kg |
| Speed controller | 149-TC12 (5 step transformer) |
| Wiring diagram | 152-540 |
Manuals & Guides
Delivery & Returns
Our Price Match Promise
Payment Methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
What duct size does the Elta SEL355/4-1AC fit?
355mm circular duct. It slides into the duct run and fixes with its integral mounting bracket, in any orientation.
How much air does the SEL355/4-1AC move?
Up to 2570 m³/h (0.714 m³/s) in free air, 2124 m³/h at 100 Pa and 108 m³/h at 250 Pa, the highest pressure in Elta's table for this model.
Which speed controller suits the SEL355/4-1AC?
Elta specify the 149-TC12 single phase 5 step transformer controller (2 A). It is available to order, so ask us for a price.
How noisy is the SEL355/4-1AC?
Elta quote 43 dB(A) inlet and 45 dB(A) outlet at 3m on full speed, with 26 dB(A) breakout. Spigot silencers from 300 to 1200mm long are available.
Can the SEL355/4-1AC be fitted outside?
No. The casing is weatherproofed to IPX4, but Elta's installation manual says SEL fans must not be operated out of doors and should be installed in dry rooms free of condensation.
What does the code SEL355/4-1AC mean?
SEL is the Multiflow range, 355 is the diameter in mm, 4 is the number of motor poles, 1 is single phase and AC is the motor type.