Elta Multiflow SEL250/2-1AC Mixed Flow Inline Fan Single Phase AC - 250mm
Suggested products
Free 14 day returns
Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.
Why choose eFans?
- Bulk pricing available
- Free help and advice
- Fast quotes, usually within the hour
- Huge range with next-day delivery
- Credit accounts available
Delivery and Warranty
Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days.
£7.95
Next Working Day Delivery
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays)
£15.95
Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95
Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95
Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95
Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95
Product Details
Downloads
Specifications
Product specifications
| Model | SEL250/2-1AC |
| Type | Mixed flow inline duct fan |
| Duct size | 250mm |
| Max airflow | 1631 m³/h |
| Static pressure | 400 Pa |
| Motor | Single phase AC, 220 to 240V 50Hz, 2 pole, 2684 rpm |
| Power | 0.162 kW (0.7 A) |
| Noise | 51 dB(A) inlet, 53 dB(A) outlet at 3m |
| IP rating | IPX4 casing, IP44 terminal box |
| Warranty | 1 Year Manufacturer |
Summary
See more specification See less specification
The Elta Multiflow SEL250/2-1AC is a 250mm mixed flow inline duct fan with a single phase 2 pole AC motor, moving up to 1631 m³/h in free air and 1465 m³/h against 100 Pa. A diagonal mixed flow impeller and 3D stator guide vanes give it far more pressure than an axial fan of the same diameter.
The motor runs at 2684 rpm on 220 to 240V 50Hz, absorbing 0.162 kW at its best efficiency point with integral thermal overload protection, and it is wired through an integral IP44 terminal box. The casing is weatherproofed to IPX4, the fan mounts at any angle on its integral bracket, and Elta give a 12 month warranty.
- 1 Phase
- AC Motor
- Up to 1631 m³/h
- Speed Controllable
What it is best used for
Compact, high pressure extract or supply on 250mm duct with a single phase supply: changing rooms, toilet blocks in sports centres and schools, small commercial kitchens behind a filtered canopy, hotel corridors and office plant. It keeps 1465 m³/h at 100 Pa and 1127 m³/h at 250 Pa from a casing only 250mm in diameter.
Its curve collapses above 250 Pa (389 m³/h at 300 Pa), so do not select it for a system that needs more than about 250 Pa. For more air or pressure on 315mm duct, see the SEL315/2A-1AC.
Why choose this over alternatives
Mixed flow gives the SEL250 far more pressure than a 250mm axial fan and a smaller casing than a centrifugal box fan, with Elta's 3D stator guide vanes turning swirl into useful pressure. Against the 250mm Jetflow SJMF250 EC fan (1606 m³/h free air), the SEL250/2-1AC moves a little more air (1631 m³/h), with simple 5 step transformer control instead of a 0-10V signal.
Installation notes
- The fan can be mounted in any orientation. Slide it into the duct and fix it with the integral mounting bracket, making sure the ductwork is not strained, and connect duct to both inlet and outlet so no moving parts are accessible.
- Elta recommend padded connection sleeves or fast clamps (018-250-CLAMP) to cut noise transmitted into the ductwork. Run the airflow in the direction marked on the casing.
- Wire into the integral IP44 terminal box to Elta diagram 152-539. Elta specify the 149-TC12 5 step transformer controller (2 A) for speed control; at lower steps the fan runs at 2435, 2100 and 1490 rpm.
- The internal thermal protection does not protect the motor if the impeller is blocked, so where that could happen fit a motor protection switch with thermal and magnetic release. Fit a means of isolation and earth the fan.
- Install indoors in a dry, condensation free space: Elta's installation manual says SEL fans must not be operated out of doors, and they are not for explosive atmospheres. Clean the impeller and casing at the recommended intervals; an upstream filter extends them.
You'll also need
- Elta 149-TC12 single phase 5 step transformer controller (2 A), available to order, ask us.
- Elta fast clamps 018-250-CLAMP (each) and backdraught damper 018-250-DAMPER, available to order, ask us.
- Elta spigot silencers 068-0250-JF1 (300mm) to 068-0250-JF4 (1200mm), available to order, ask us.
Browse more inline mixed flow fans, inline duct fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SEL250/2-1AC |
| Type | Mixed flow inline duct fan |
| Duct size | 250mm |
| Max airflow | 1631 m³/h |
| Static pressure | 400 Pa |
| Motor | Single phase AC, 220 to 240V 50Hz, 2 pole, 2684 rpm |
| Power | 0.162 kW (0.7 A) |
| Noise | 51 dB(A) inlet, 53 dB(A) outlet at 3m |
| IP rating | IPX4 casing, IP44 terminal box |
| Warranty | 1 Year Manufacturer |
| Airflow at 100 Pa | 1465 m³/h |
| Airflow at 200 Pa | 1260 m³/h |
| Overall efficiency | 46.9% at best efficiency point |
| FMEG efficiency grade | N 65.7 |
| Max ambient temperature | 50°C (nameplate) |
| Breakout noise | 29 dB(A) at 3m |
| Weight | 5 kg |
| Speed controller | 149-TC12 (5 step transformer) |
| Wiring diagram | 152-539 |
Manuals & Guides
Product Description
The Elta Multiflow SEL250/2-1AC is a 250mm mixed flow inline duct fan with a single phase 2 pole AC motor, moving up to 1631 m³/h in free air and 1465 m³/h against 100 Pa. A diagonal mixed flow impeller and 3D stator guide vanes give it far more pressure than an axial fan of the same diameter.
The motor runs at 2684 rpm on 220 to 240V 50Hz, absorbing 0.162 kW at its best efficiency point with integral thermal overload protection, and it is wired through an integral IP44 terminal box. The casing is weatherproofed to IPX4, the fan mounts at any angle on its integral bracket, and Elta give a 12 month warranty.
- 1 Phase
- AC Motor
- Up to 1631 m³/h
- Speed Controllable
What it is best used for
Compact, high pressure extract or supply on 250mm duct with a single phase supply: changing rooms, toilet blocks in sports centres and schools, small commercial kitchens behind a filtered canopy, hotel corridors and office plant. It keeps 1465 m³/h at 100 Pa and 1127 m³/h at 250 Pa from a casing only 250mm in diameter.
Its curve collapses above 250 Pa (389 m³/h at 300 Pa), so do not select it for a system that needs more than about 250 Pa. For more air or pressure on 315mm duct, see the SEL315/2A-1AC.
Why choose this over alternatives
Mixed flow gives the SEL250 far more pressure than a 250mm axial fan and a smaller casing than a centrifugal box fan, with Elta's 3D stator guide vanes turning swirl into useful pressure. Against the 250mm Jetflow SJMF250 EC fan (1606 m³/h free air), the SEL250/2-1AC moves a little more air (1631 m³/h), with simple 5 step transformer control instead of a 0-10V signal.
Installation notes
- The fan can be mounted in any orientation. Slide it into the duct and fix it with the integral mounting bracket, making sure the ductwork is not strained, and connect duct to both inlet and outlet so no moving parts are accessible.
- Elta recommend padded connection sleeves or fast clamps (018-250-CLAMP) to cut noise transmitted into the ductwork. Run the airflow in the direction marked on the casing.
- Wire into the integral IP44 terminal box to Elta diagram 152-539. Elta specify the 149-TC12 5 step transformer controller (2 A) for speed control; at lower steps the fan runs at 2435, 2100 and 1490 rpm.
- The internal thermal protection does not protect the motor if the impeller is blocked, so where that could happen fit a motor protection switch with thermal and magnetic release. Fit a means of isolation and earth the fan.
- Install indoors in a dry, condensation free space: Elta's installation manual says SEL fans must not be operated out of doors, and they are not for explosive atmospheres. Clean the impeller and casing at the recommended intervals; an upstream filter extends them.
You'll also need
- Elta 149-TC12 single phase 5 step transformer controller (2 A), available to order, ask us.
- Elta fast clamps 018-250-CLAMP (each) and backdraught damper 018-250-DAMPER, available to order, ask us.
- Elta spigot silencers 068-0250-JF1 (300mm) to 068-0250-JF4 (1200mm), available to order, ask us.
Browse more inline mixed flow fans, inline duct fans or Elta fans, or call us for help choosing the right fan.
Specifications
| Model | SEL250/2-1AC |
| Type | Mixed flow inline duct fan |
| Duct size | 250mm |
| Max airflow | 1631 m³/h |
| Static pressure | 400 Pa |
| Motor | Single phase AC, 220 to 240V 50Hz, 2 pole, 2684 rpm |
| Power | 0.162 kW (0.7 A) |
| Noise | 51 dB(A) inlet, 53 dB(A) outlet at 3m |
| IP rating | IPX4 casing, IP44 terminal box |
| Warranty | 1 Year Manufacturer |
| Airflow at 100 Pa | 1465 m³/h |
| Airflow at 200 Pa | 1260 m³/h |
| Overall efficiency | 46.9% at best efficiency point |
| FMEG efficiency grade | N 65.7 |
| Max ambient temperature | 50°C (nameplate) |
| Breakout noise | 29 dB(A) at 3m |
| Weight | 5 kg |
| Speed controller | 149-TC12 (5 step transformer) |
| Wiring diagram | 152-539 |
Manuals & Guides
Delivery & Returns
Our Price Match Promise
Payment Methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
What duct size does the Elta SEL250/2-1AC fit?
250mm circular duct. It slides into the duct run and fixes with its integral mounting bracket, in any orientation.
How much air does the SEL250/2-1AC move?
Up to 1631 m³/h (0.453 m³/s) in free air, 1465 m³/h at 100 Pa and 112 m³/h at 400 Pa, the highest pressure in Elta's table for this model.
Which speed controller suits the SEL250/2-1AC?
Elta specify the 149-TC12 single phase 5 step transformer controller (2 A). It is available to order, so ask us for a price.
How noisy is the SEL250/2-1AC?
Elta quote 51 dB(A) inlet and 53 dB(A) outlet at 3m on full speed, with 29 dB(A) breakout. Spigot silencers from 300 to 1200mm long are available.
Can the SEL250/2-1AC be fitted outside?
No. The casing is weatherproofed to IPX4, but Elta's installation manual says SEL fans must not be operated out of doors and should be installed in dry rooms free of condensation.
What does the code SEL250/2-1AC mean?
SEL is the Multiflow range, 250 is the diameter in mm, 2 is the number of motor poles, 1 is single phase and AC is the motor type.