Elta HAVA400V Vertical MVHR Heat Recovery Unit - 403 m³/h
Suggested products
Free 14 day returns
Changed your mind or ordered the wrong unit? You have 14 days from delivery to send it back. As long as items are unused and in their original packaging, we'll arrange your refund. Just contact our team and we'll take care of the rest. Made-to-order and bespoke items are non-returnable.
Why choose eFans?
- Bulk pricing available
- Free help and advice
- Fast quotes, usually within the hour
- Huge range with next-day delivery
- Credit accounts available
Delivery and Warranty
Standard UK Mainland Delivery
If you are not in a rush, then we offer standard delivery and your order should be with you between 2-3 working days.
£7.95
Next Working Day Delivery
Place your order before 12pm Monday to Thursday and receive your order the next working day. Orders placed on Friday before 11am will be processed and delivered on Monday. (Excludes Sunday’s and Public Holidays)
£15.95
Nominated Day Delivery
We know sometimes you will need an order on a particular date in the future. Simply select this option at checkout and add what date you would like to receive the order. We will then contact you to confirm the date. If you need to change this order date then please contact us ASAP.
£15.95
Northern Ireland Delivery
We offer a flat fee rate for Northern Ireland orders, and all are 5-7 working day lead times.
£29.95
Scottish Highlands & Islands Delivery
We only offer a flat fee rate for Scottish Highland & Islands orders, and all are 5-7 working day lead times.
£45.95
Channel Islands Delivery
We only offer a flat fee rate for Channel Islands orders, and all are 5-7 working day lead times.
£45.95
Product Details
Downloads
Specifications
Product specifications
| Model | HAVA400V |
| Brand | Elta |
| Type | Whole house MVHR unit |
| Max airflow | 112 l/s (403 m³/h), 100 l/s at 100 Pa |
| Heat recovery efficiency | Up to 84% |
| SFP | 0.60 W/(l/s) at 29 l/s |
| Spigots | 4 x 155mm |
| Max power | 160 W |
| Sound | 26 dB(A) at 3m (breakout, 40% speed) |
| Controller | CTRL-DSP LCD controller with 3 speeds, boost, night, holiday and weekly timer, supplied |
Summary
See more specification See less specification
The Elta HAVA400V is a whole house MVHR unit that extracts stale, humid air from wet rooms and supplies fresh, filtered air to living rooms and bedrooms, recovering up to 84% of the heat through a counterflow plate heat exchanger. It moves up to 112 l/s (403 m³/h), or 100 l/s against 100 Pa.
The EPP construction sits in metal casework, with automatic anti-frost protection and an integral summer bypass. It comes pre-cabled with the CTRL-DSP LCD controller and is PCDB and SAP Appendix Q listed, with Elta SAP data up to kitchen + 7 wet rooms.
- Up to 84% heat recovery
- Up to 403 m³/h
- Vertical, wall mounted
- PCDB and SAP Appendix Q listed
What it is best used for
Four and five bedroom houses with up to seven wet rooms plus a kitchen, wall mounted in a utility, plant room or cupboard. Its specific fan power stays low across the range, 0.60 to 1.24 W/(l/s) in the SAP data.
Heat exchange efficiency is lower than the HAVA280V and HAVA550V at the same settings (84% at kitchen plus 1), so if SAP efficiency matters more than fan power compare those first.
Why choose this over alternatives
MVHR keeps an airtight new build or deep retrofit ventilated around the clock while recovering most of the heat that trickle vents and extract fans throw away, which helps with Part F and the SAP assessment. The HAVA400V adds night mode, holiday mode and a weekly timer on the supplied LCD controller, so occupants can run it quietly overnight without switching it off.
The Elta HAVA550V shares the same 861 x 778 x 549mm casing but moves up to 153 l/s with heat exchange of 87 to 90% in the SAP data.
Installation notes
- Mount indoors in a heated space, vertically on a flat wall that carries its weight. It must be vertical for the condensate drainage to work.
- Connect a G 3/4 inch condensate drain joint through a U-bend or dry trap and plug the unused one. Leave access to the filters and inspection doors.
- The outside air connections can be handed left or right: change the orientation in the CTRL-DSP installer menu and swap the duct and drain labels supplied.
- Connect the CTRL-DSP with a 4 core twisted pair cable up to 30m. A humidity or air quality sensor on the IAQ input raises the speed by 15%.
- Insulate the ductwork to local regulations, commission the supply and extract rates, and clean the heat exchanger once a year with a vacuum cleaner.
You'll also need
- Elta SEN-HY-I wall mounted humidity sensor wires to the unit's volt free sensor input to boost ventilation when humidity rises.
- F7 (ISO ePM1 60%) filters available on request for better supply air filtration, ask us.
Browse more whole house MVHR units, heat recovery units or rigid ducting, or call us for help choosing the right product.
Specifications
| Model | HAVA400V |
| Brand | Elta |
| Type | Whole house MVHR unit |
| Max airflow | 112 l/s (403 m³/h), 100 l/s at 100 Pa |
| Heat recovery efficiency | Up to 84% |
| SFP | 0.60 W/(l/s) at 29 l/s |
| Spigots | 4 x 155mm |
| Max power | 160 W |
| Sound | 26 dB(A) at 3m (breakout, 40% speed) |
| Controller | CTRL-DSP LCD controller with 3 speeds, boost, night, holiday and weekly timer, supplied |
| Orientation | Vertical |
| Heat exchanger | Counterflow plate |
| Filters | G4 (ISO Coarse 60%), F7 on request |
| Summer bypass | Integral automatic |
| Frost protection | Automatic |
| Max ambient temperature | 40°C |
| Weight | 34.5 kg |
| Dimensions | 861 x 778 x 549mm (H x W x D) |
| Listing | PCDB and SAP Appendix Q |
| SAP: Kitchen + 1 wet room | 21 l/s, SFP 0.64, 84% |
| SAP: Kitchen + 2 wet rooms | 29 l/s, SFP 0.60, 84% |
| SAP: Kitchen + 3 wet rooms | 37 l/s, SFP 0.63, 84% |
| SAP: Kitchen + 4 wet rooms | 45 l/s, SFP 0.72, 83% |
| SAP: Kitchen + 5 wet rooms | 53 l/s, SFP 0.85, 82% |
| SAP: Kitchen + 6 wet rooms | 61 l/s, SFP 1.03, 82% |
| SAP: Kitchen + 7 wet rooms | 69 l/s, SFP 1.24, 81% |
Manuals & Guides
Product Description
The Elta HAVA400V is a whole house MVHR unit that extracts stale, humid air from wet rooms and supplies fresh, filtered air to living rooms and bedrooms, recovering up to 84% of the heat through a counterflow plate heat exchanger. It moves up to 112 l/s (403 m³/h), or 100 l/s against 100 Pa.
The EPP construction sits in metal casework, with automatic anti-frost protection and an integral summer bypass. It comes pre-cabled with the CTRL-DSP LCD controller and is PCDB and SAP Appendix Q listed, with Elta SAP data up to kitchen + 7 wet rooms.
- Up to 84% heat recovery
- Up to 403 m³/h
- Vertical, wall mounted
- PCDB and SAP Appendix Q listed
What it is best used for
Four and five bedroom houses with up to seven wet rooms plus a kitchen, wall mounted in a utility, plant room or cupboard. Its specific fan power stays low across the range, 0.60 to 1.24 W/(l/s) in the SAP data.
Heat exchange efficiency is lower than the HAVA280V and HAVA550V at the same settings (84% at kitchen plus 1), so if SAP efficiency matters more than fan power compare those first.
Why choose this over alternatives
MVHR keeps an airtight new build or deep retrofit ventilated around the clock while recovering most of the heat that trickle vents and extract fans throw away, which helps with Part F and the SAP assessment. The HAVA400V adds night mode, holiday mode and a weekly timer on the supplied LCD controller, so occupants can run it quietly overnight without switching it off.
The Elta HAVA550V shares the same 861 x 778 x 549mm casing but moves up to 153 l/s with heat exchange of 87 to 90% in the SAP data.
Installation notes
- Mount indoors in a heated space, vertically on a flat wall that carries its weight. It must be vertical for the condensate drainage to work.
- Connect a G 3/4 inch condensate drain joint through a U-bend or dry trap and plug the unused one. Leave access to the filters and inspection doors.
- The outside air connections can be handed left or right: change the orientation in the CTRL-DSP installer menu and swap the duct and drain labels supplied.
- Connect the CTRL-DSP with a 4 core twisted pair cable up to 30m. A humidity or air quality sensor on the IAQ input raises the speed by 15%.
- Insulate the ductwork to local regulations, commission the supply and extract rates, and clean the heat exchanger once a year with a vacuum cleaner.
You'll also need
- Elta SEN-HY-I wall mounted humidity sensor wires to the unit's volt free sensor input to boost ventilation when humidity rises.
- F7 (ISO ePM1 60%) filters available on request for better supply air filtration, ask us.
Browse more whole house MVHR units, heat recovery units or rigid ducting, or call us for help choosing the right product.
Specifications
| Model | HAVA400V |
| Brand | Elta |
| Type | Whole house MVHR unit |
| Max airflow | 112 l/s (403 m³/h), 100 l/s at 100 Pa |
| Heat recovery efficiency | Up to 84% |
| SFP | 0.60 W/(l/s) at 29 l/s |
| Spigots | 4 x 155mm |
| Max power | 160 W |
| Sound | 26 dB(A) at 3m (breakout, 40% speed) |
| Controller | CTRL-DSP LCD controller with 3 speeds, boost, night, holiday and weekly timer, supplied |
| Orientation | Vertical |
| Heat exchanger | Counterflow plate |
| Filters | G4 (ISO Coarse 60%), F7 on request |
| Summer bypass | Integral automatic |
| Frost protection | Automatic |
| Max ambient temperature | 40°C |
| Weight | 34.5 kg |
| Dimensions | 861 x 778 x 549mm (H x W x D) |
| Listing | PCDB and SAP Appendix Q |
| SAP: Kitchen + 1 wet room | 21 l/s, SFP 0.64, 84% |
| SAP: Kitchen + 2 wet rooms | 29 l/s, SFP 0.60, 84% |
| SAP: Kitchen + 3 wet rooms | 37 l/s, SFP 0.63, 84% |
| SAP: Kitchen + 4 wet rooms | 45 l/s, SFP 0.72, 83% |
| SAP: Kitchen + 5 wet rooms | 53 l/s, SFP 0.85, 82% |
| SAP: Kitchen + 6 wet rooms | 61 l/s, SFP 1.03, 82% |
| SAP: Kitchen + 7 wet rooms | 69 l/s, SFP 1.24, 81% |
Manuals & Guides
Delivery & Returns
Our Price Match Promise
Payment Methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
What size home is the HAVA400V for?
Elta publish SAP data up to kitchen + 7 wet rooms, which suits four and five bedroom houses with the unit wall mounted.
How efficient is it?
Heat recovery up to 84% with SFP of 0.60 W/(l/s) at 29 l/s in the SAP Appendix Q data.
Is it SAP listed?
Yes, it is PCDB and SAP Appendix Q listed, so its tested performance can be used in SAP calculations.
Does it have a summer bypass?
Yes, an integral automatic summer bypass, set up in the CTRL-DSP installer menu, with automatic anti-frost protection as well.
What filters does it use?
G4 (ISO Coarse 60%), F7 on request. A filter warning on the controller tells the user when they need cleaning.
Does it need a condensate drain?
Yes. Condensation forms on the heat exchanger, so the drain must be connected through a U-bend or dry trap to waste.